Single Conductor 600V Secondary Type URD Cable Aluminum Conductor

Check up to five results to perform an action.

Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.

Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
  • B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
  • Secondary UD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request.
Options
  • Cable in Duct (CIC)
  • Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 16 of 16 1 

Item #

Size
AWG or MCM

Stranding

Outside
Diameter

Weight
Per
MFT

Ampacity
Direct Burial

Ampacity
In Duct

Princeton 6 7/W .298 Inches 45 Lbs 90 Amps 65 Amps
Mercer 4 7/W .345 Inches 64 Lbs 120 Amps 85 Amps
Clemson 2 7/W .403 Inches 93 Lbs 155 Amps 115 Amps
Kenyon 1 19/W .522 Inches 148 Lbs 200 Amps 150 Amps
Harvard 1/0 19/W .482 Inches 122 Lbs 175 Amps 130 Amps
Yale 2/0 19/W .566 Inches 179 Lbs 225 Amps 170 Amps
Tufts 3/0 19/W .616 Inches 217 Lbs 250 Amps 195 Amps
Beloit 4/0 19/W .672 Inches 265 Lbs 290 Amps 225 Amps
Hofstra 250 37/W .748 Inches 317 Lbs 320 Amps 250 Amps
Gonzaga 300 37/W .801 Inches 371 Lbs 355 Amps 280 Amps
Rutgers 350 37/W .851 Inches 423 Lbs 385 Amps 305 Amps
Emory 500 37/W .979 Inches 579 Lbs 465 Amps 370 Amps
Duke 600 61/W 1.086 Inches 701 Lbs 510 Amps 410 Amps
Furman 700 61/W 1.155 Inches 804 Lbs 550 Amps 440 Amps
Sewanee 750 61/W 1.188 Inches 855 Lbs 580 Amps 470 Amps
Fordham 1000 61/W 1.337 Inches 1109 Lbs 670 Amps 545 Amps