Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts. Especially suited for applications requiring superior resistance to mechanical damage. Rated 90°C continuous operation, 130°C emergency overload and short circuit 250°C.

Construction
Conductors are stranded, compressed 1350-H16/H26 aluminum, insulated with a cross-linked polyethylene meeting the requirements of ANSI/ICEA S-81-570. Neutrals are triple yellow extruded stripe and have sequential footage markers. Conductors are durably surface printed for identification.

Standards
Ruggedized duplex 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications:

• B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
• B-609 Aluminum 1350 Round Wire, Annealed and Intermidiate Tempers, for Electrical Purposes.
• B-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent Insulation.
• B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.

Ruggedized triplex 600 volt secondary UD cable insulation meets or exceeds all grade and type requirements of ICEA S-81-570 and UL Standard 854 for Type USE-2.


Notes
+Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO factor 90. For NEC Applications, use NEC Table 310.16 Ampacities.






    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 2 of 2 1 

Item #

Phase
Conductor
Size/AWG

Phase
Conductor
Stranding

Phase
Conductor
Insulation
Thickness
(mils)

Neutral
Size
AWG

Neutral
Stranding

Neutral
Conductor
Insulation
Thickness
(mils)

Diameter
Single
Phase
Conductor
(mils)

Diameter
Neutral
Conductor
(mils)

Diameter
Complete
Cable
(mils)

Weight
(lbs/MFT)

Allowable
Ampacities+
Direct Burial

Allowable
Ampacities+
In
Duct

Claflin/R 6 7 60 6 7 60 298 298 596 90 90 65