All Categories > Control Cables & Portable Power Cables > Control Cables > Control Cable/Power Cable FR-XLPE > Control Cable/Power Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER > Control Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER > 14 AWG Control Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER > View Items  

14 AWG Control Cable FR-XLPE Insulated Conductors, Copper Tape Shield, PVC Jacket, 600V UL Type TC or TC-ER

Check up to five results to perform an action.

Applications

As flame-retardant multi-conductor control, signal or power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.

Construction

Stranded uncoated copper conductors, 30 mils FR-XLPE flame-retardant cross-linked polyethylene insulation, color coded, conductors twisted with suitable fillers where necessary to make round, cable tape, helically applied copper tape shield, PVC jacket overall, surface printed.

Specifications

  • Listed by UL as Type TC or TC-ER per Standard 1277 for Tray Cables.
  • Cables UL listed for Direct Burial.
  • Individual conductors pass UL VW-1 flame test.
  • Individual conductors UL listed as Type XHHW-2.
  • Overall jacket UL listed as Sunlight Resistant.
  • Cables with grounding conductor UL listed for Open Wiring.
  • Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
  • Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
  • Cables meet requirements of ICEA S-73-532, NEMA WC57 for Control Cables.

Notes

  • Cables may be supplied with an insulated ground and marked “Open Wiring.”
  • Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73- 532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 12 of 12 1 

Item #

Conductor
Size
AWG

Number
of
Conductors

O.A.
(mils)

O.D.
(inch)

Weight
(lb/MFT)

14-02XHPTCS 14 2 45 0.38 77
14-03XHPTCS 14 3 45 0.4 97
14-04XHPTCS 14 4 45 0.44 121
14-05XHPTCS 14 5 45 0.48 145
14-07XHPTCS 14 7 45 0.6 182
14-09XHPTCS 14 9 60 0.63 252
14-12XHPTCS 14 12 60 0.69 309
14-15XHPTCS 14 15 60 0.77 413
14-19XHPTCS 14 19 60 0.81 468
14-25XHPTCS 14 25 80 1 651
14-31XHPTCS 14 31 80 1.07 761
14-37XHPTCS 14 37 80 1.14 900