Aluminum 3/Conductor UL Type TC 600V

Check up to five results to perform an action.

Applications

These cables are specifically approved for power, control, lighting and signal circuits, in manufacturing, industrial and commercial installations. For use in direct burial, in cable trays, in raceways, or where supported in outdoor locations by a messenger wire.

In cable tray in hazardous (classified) locations Class I, Division 2 per NEC, also as Class I circuits per Article 725, and in Class II, Division 2, as permitted per NEC. When installed in accordance with NEC 336.10(7), TC-ER marked cable is approved for use as open wiring between a cable tray and the utilization equipment or device.

Construction

Assembly consisting of three or four insulated aluminum alloy AA8000 compact stranded conductors, cabled together with a bare equipment grounding conductor and non-hygroscopic fillers. The sub-assembly is wrapped with binding tape and a PVC jacket is applied over the taped assembly. PVC jacket is sunlight resistant, moisture resistant and flame retardant.  This cable uses XHHW-2 conductors that are phase identified, including one insulated black conductor, one insulated white conductor, and one insulated conductor with a single longitudinal red stripe. If required, a fourth insulated conductor has a single longitudinal blue stripe.  Phase conductors are insulated with cross-linked polyethylene (XLPE) and rated for a maximum operating temperature of 90° C in dry and wet locations, rated for 600 volts maximum operating voltage.  Insulation is free of harmful heavy metals in compliance with RoHS, Directive 2002/95/EC. 

Standards

  • UL 1277 Type TC Tray Cable
  • UL 44 Thermoset Insulated Conductors, Type XHHW-2 or RHW-2
  • ICE A S-73-5 32
  • NEMA WC57 Standard for Control Cables.
  • ICE A S-95-658 Standard for Non-shielded Power Cables Rated 2000 Volts or Less.

Notes

  • Terminates safely with industry standard dual rated terminals and connectors





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 20 of 20 1 

Item #

Conductor
Size
(AWG
or
kcmil)

No.
of
Phase
Conductors

Grounding
Conductor
(AWG
or
kcmil)

Insulation
Thickness
(mils)

Jacket
Thickness
(mils)

Nominal
Diameter
(inches)

Nominal
Weight
(LBS/MFT)

Package
Length
(feet)

Ampacity
90°C

Ampacity
75°C

A6-03XHPGTC-6 6 3 6 45 60 0.76 234 1000 75 50
A4-03XHPGTC-6 4 3 6 45 60 0.82 293 1000 75 65
A2-03XHPGTC-6 2 3 6 45 80 0.95 431 1000 100 90
A1-03XHPGTC-4 1 3 4 55 80 1.08 544 1000 115 100
A1/0-03XHPGTC-4 1/0 3 4 55 80 1.14 629 1000 135 120
A2/0-03XHPGTC-4 2/0 3 4 55 80 1.22 739 1000 150 135
A3/0-03XHPGTC-4 3/0 3 4 55 80 1.32 872 1000 175 155
A4/0-03XHPGTC-2 4/0 3 2 55 80 1.43 1061 1000 205 180
A250-03XHPGTC-2 250 3 2 65 80 1.57 1238 500 230 205
A300-03XHPGTC-2 300 3 2 65 110 1.74 1524 500 260 230
A300-03XHPGTC-1/0 300 3 1/0 65 110 1.74 1559 500 260 230
A350-03XHPGTC-2 350 3 2 65 110 1.83 1711 500 280 250
A400-03XHPGTC-1 400 3 1 65 110 1.94 1888 500 305 270
A500-03XHPGTC-1 500 3 1 65 110 2.11 2251 500 350 310
A600-03XHPGTC-1 600 3 1 80 110 2.34 2692 500 385 340
A700-03XHPGTC-1/0 700 3 1/0 80 110 2.47 3069 500 425 375
A750-03XHPGTC-1/0 750 3 1/0 80 110 2.54 3244 500 435 385
A900-03XHPGTC-250 900 3 250 80 140 2.80 4059 500 480 425
A900-03XHPGTC-400 900 3 400 80 140 2.91 4271 500 480 425
A900-03XHPGTC-750 900 3 750 80 140 3.19 5786 500 480 425
  Results 1 - 20 of 20 1 