ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
All Categories > Control Cables & Portable Power Cables > Control Cables > THHN/PVC Tray Cable (Type TC) 600V > TFN, THWN, or THHN - PVC Jacket, 600V > 16 AWG TFN PVC Jacket, 600V, 2/C - 37/C > View Items  

16 AWG TFN PVC Jacket, 600V, 2/C - 37/C

Check up to five results to perform an action.

Applications
As flame-retardant multi-conductor control, signal or power cables rated 600 volts, 90 Deg. C. in dry locations, 75 Deg. C. in wet locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class 1 remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.

Construction
Individual conductors of stranded uncoated copper Type TFN (16AWG). Type THWN or THHN (14-10 AWG), color coded, two conductors flat, three or more conductors twisted, PVC jacket overall, surface printed.

Standards
  1. Listed by UL as Type TC Tray Cable per Article 336 of the NEC.
  2. Individual conductors UL listed as Type THWN or THHN (14-10 AWG) or Type TFN (16 AWG).
  3. Overall jacket UL listed as Sunlight Resistant.
  4. Cables UL listed for Direct Burial.
  5. Cables with grounding conductor UL listed for Open Wiring.
  6. Cables pass UL and IEEE-383 ribbon burner tests and ICEA 210.00 BTU/hour test.
Notes
  • Cables designated (w/g) contain an additional bare copper grounding conductor, same size as circuit conductors, and are UL listed for Open Wiring.
  • Standard color coding is ICEA Method E2 or K2 for NEC applications. This color coding method omits white and green from the color sequence.
  • ICEA Method 4 color coding is also provided. This consists of printed numbers and words, 1-ONE, 2-TWO, etc.
  • Size 16 AWG is rated 90 ºC dry only.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 27 of 27 1 

Item #

Number
of
Conductors

Size
AWG

Number
of
Strands

Overall
PVC Jacket
(mils)

Nominal
Diameter
(in)

16-TC1-2 2 16 7 45 .20 x .30
16-TC1-3 3 16 7 45 0.32
16-TC1-3 w/g 3 w/g 16 7 N/A N/A
16-TC1-4 4 16 7 45 0.34
16-TC1-5 5 16 7 45 0.37
16-TC1-6 6 16 7 45 0.40
16-TC1-7 7 16 7 45 0.40
16-TC1-8 8 16 7 45 0.44
16-TC1-9 9 16 7 45 0.47
16-TC1-10 10 16 7 45 0.51
16-TC1-11 11 16 7 45 0.51
16-TC1-12 12 16 7 60 0.55
16-TC1-13 13 16 7 60 0.56
16-TC1-14 14 16 7 60 0.58
16-TC1-15 15 16 7 60 0.61
16-TC1-16 16 16 7 60 0.61
16-TC1-17 17 16 7 60 0.64
16-TC1-18 18 16 7 60 0.64
16-TC1-19 19 16 7 60 0.64
16-TC1-20 20 16 7 60 0.67
16-TC1-23 23 16 7 60 0.70
16-TC1-25 25 16 7 60 0.74
16-TC1-27 27 16 7 60 0.76
16-TC1-29 29 16 7 60 0.77
16-TC1-31 31 16 7 60 0.80
16-TC1-32 32 16 7 60 0.82
16-TC1-37 37 16 7 80 0.89
  Results 1 - 27 of 27 1 