A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 25 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000 V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Options
  • EPR insulation
  • Filled strand
  • Cable core water blocking
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100 % load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC operating at 105 ºC conductor (NEC Table 310.73).
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 5 of 5 | Results Per Page | View | Unit of Measure
1 

Item #

Code Name

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
1/C
Direct
Buried

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Duct In Air

260-TRXLP-18 N/A Handel N/A 1 N/A 19 N/A 13 N/A 12 N/A 0.322 Inches N/A 0.900 Inches N/A 0.980 Inches N/A 1.142 Inches N/A 1.242 Inches N/A 615 Lbs N/A 701 Lbs N/A 245 Amps N/A 185 Amps N/A 162 Amps
260-TRXLP-19 N/A Haydn N/A 1/0 N/A 19 N/A 16 N/A 12 N/A 0.362 Inches N/A 0.940 Inches N/A 1.022 Inches N/A 1.184 Inches N/A 1.284 Inches N/A 1044 Lbs N/A 1133 Lbs N/A 280 Amps N/A 215 Amps N/A 189 Amps
260-TRXLP-20 N/A Brahms N/A 2/0 N/A 19 N/A 20 N/A 12 N/A 0.405 Inches N/A 0.985 Inches N/A 1.065 Inches N/A 1.227 Inches N/A 1.327 Inches N/A 1232 Lbs N/A 1321 Lbs N/A 315 Amps N/A 240 Amps N/A 210 Amps
260-TRXLP-21 N/A Ravel N/A 3/0 N/A 19 N/A 25 N/A 12 N/A 0.456 Inches N/A 1.035 Inches N/A 1.155 Inches N/A 1.317 Inches N/A 1.417 Inches N/A 1502 Lbs N/A 1594 Lbs N/A 360 Amps N/A 275 Amps N/A 241 Amps
260-TRXLP-22 N/A Chopin N/A 4/0 N/A 19 N/A 32 N/A 12 N/A 0.512 Inches N/A 1.090 Inches N/A 1.210 Inches N/A 1.372 Inches N/A 1.472 Inches N/A 1828 Lbs N/A 1919 Lbs N/A 415 Amps N/A 315 Amps N/A 276 Amps