A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 15 kV phase to phase at 100 % and 133 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000 V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Options
  • EPR insulation
  • Filled strand
  • Cable core water blocking
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100% load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC operating at 105 ºC conductor (NEC Table 310.73).
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 6 of 6 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
1/C
Direct
Buried

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Duct In Air

220-TRXLP-20 N/A 2 N/A 7 N/A 16 N/A 14 N/A 0.283 Inches N/A 0.785 Inches N/A 0.865 Inches N/A 0.993 Inches N/A 1.093 Inches N/A 695 Lbs N/A 760 Lbs N/A 225 Amps N/A 160 Amps N/A 140 Amps
220-TRXLP-21 N/A 1 N/A 19 N/A 13 N/A 12 N/A 0.322 Inches N/A 0.820 Inches N/A 0.900 Inches N/A 1.062 Inches N/A 1.162 Inches N/A 559 Lbs N/A 633 Lbs N/A 260 Amps N/A 185 Amps N/A 162 Amps
220-TRXLP-22 N/A 1/0 N/A 19 N/A 16 N/A 12 N/A 0.362 Inches N/A 0.860 Inches N/A 0.940 Inches N/A 1.102 Inches N/A 1.202 Inches N/A 982 Lbs N/A 1060 Lbs N/A 295 Amps N/A 210 Amps N/A 185 Amps
220-TRXLP-23 N/A 2/0 N/A 19 N/A 20 N/A 12 N/A 0.405 Inches N/A 0.905 Inches N/A 0.985 Inches N/A 1.147 Inches N/A 1.247 Inches N/A 1169 Lbs N/A 1246 Lbs N/A 330 Amps N/A 240 Amps N/A 210 Amps
220-TRXLP-24 N/A 3/0 N/A 19 N/A 25 N/A 12 N/A 0.456 Inches N/A 0.955 Inches N/A 1.035 Inches N/A 1.197 Inches N/A 1.293 Inches N/A 1399 Lbs N/A 1475 Lbs N/A 375 Amps N/A 270 Amps N/A 237 Amps
220-TRXLP-25 N/A 4/0 N/A 19 N/A 32 N/A 12 N/A 0.512 Inches N/A 1.010 Inches N/A 1.090 Inches N/A 1.294 Inches N/A 1.394 Inches N/A 1747 Lbs N/A 1825 Lbs N/A 430 Amps N/A 305 Amps N/A 268 Amps