All Categories > Medium Voltage Cables > 15-35kV Primary URD Concentric Neutral AEIC CS8-07 > 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 > TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 > 175 MIL TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 One Third Neutral, Aluminum Conductor > View Items  

175 MIL TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 One Third Neutral, Aluminum Conductor

Check up to five results to perform an action.

Applications
For use on single phase and three-phase primary underground distribution systems operating at 15kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
  • UL-1072 MV90
Options
  • EPR insulation
  • Filled strand
  • Cable core water blocking
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100 % load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC; operating at 105 ºC conductor (NEC Table 310.73).
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 10 of 10 1 

Item #

Code Name

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

175-TRXLP-10 Gable 1/0 Solid 6 14 230 Amps 165 Amps 145 Amps
175-TRXLP-11 N/A 1/0 19 6 14 230 Amps 165 Amps 145 Amps
175-TRXLP-12 N/A 2/0 19 7 14 250 Amps 190 Amps 167 Amps
175-TRXLP-13 N/A 3/0 19 9 14 280 Amps 215 Amps 189 Amps
175-TRXLP-14 N/A 4/0 19 11 14 320 Amps 245 Amps 215 Amps
175-TRXLP-15 Degas 250 37 13 14 345 Amps 270 Amps 237 Amps
175-TRXLP-16 Hals 350 37 11 12 405 Amps 325 Amps 285 Amps
175-TRXLP-17 Bosch 500 37 16 12 460 Amps 385 Amps 338 Amps
175-TRXLP-18 Vernet 750 61 15 10 515 Amps 475 Amps 417 Amps
175-TRXLP-19 N/A 1000 61 20 10 565 Amps 540 Amps 475 Amps