ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
All Categories > Medium Voltage Cables > 15-35kV Primary URD Concentric Neutral AEIC CS8-07 > 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 > TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 > 220 MIL TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 One Third Neutral, Copper Conductor > View Items  

220 MIL TRXLP 15kV Primary URD Concentric Neutral LLDPE Jacket AEIC CS8-07 One Third Neutral, Copper Conductor

Check up to five results to perform an action.

Applications
For use on single phase and three phase primary underground distribution systems operating at 15 kV phase to phase at 100 % and 133 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
  • UL-1072 MV90
Options
  • EPR insulation
  • Filled strand
  • Cable core water blocking
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100% load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC operating at 105 ºC conductor (NEC Table 310.73).
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 9 of 9 1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

220-TRXLP-26 1/0 19 9 14 290 Amps 210 Amps 185 Amps
220-TRXLP-27 2/0 19 11 14 320 Amps 240 Amps 210 Amps
220-TRXLP-28 3/0 19 14 14 350 Amps 275 Amps 241 Amps
220-TRXLP-29 4/0 19 11 12 390 Amps 315 Amps 276 Amps
220-TRXLP-30 250 37 13 12 415 Amps 340 Amps 298 Amps
220-TRXLP-31 350 37 12 10 475 Amps 415 Amps 364 Amps
220-TRXLP-32 500 37 17 10 525 Amps 480 Amps 420 Amps
220-TRXLP-33 750 61 25 10 560 Amps 530 Amps 465 Amps
220-TRXLP-34 1000 61 33 10 600 Amps 590 Amps 518 Amps
  Results 1 - 9 of 9 1 
Privacy     Site Map     Catalog IndexSite created by Thomas Web Solutions and Powered by Navigator Platform© 2021, American Wire Group