Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor

Check up to five results to perform an action.

Applications
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.

Construction
Conductors are stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) to produce the triplex cable configuration, or parallel if so specified. Black neutrals may be specified if desired.

Standards
Secondary URD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
  • B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
  • Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request.
Options
  • Cable in Duct (CIC)
  • Abrasion Resistant


Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 50, 100% load factor for three conductors triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 17 of 17 1 

Item #

Phase
Conductor
Size/AWG

Phase
Conductor
Stranding

Neutral Size AWG

Neutral Stranding

Ampacity
Direct Burial

Ampacity
In Duct

Erskine 6 7/w 6 7/w 95 Amps 70 Amps
Vassar 4 7/w 4 7/w 125 Amps 90 Amps
Stephens 2 7/w 4 7/w 165 Amps 120 Amps
Ramapo 2 7/w 2 7/w 165 Amps 120 Amps
Brenau 1/0 19/w 2 7/w 215 Amps 160 Amps
Bergen 1/0 19/w 1/0 19/w 215 Amps 160 Amps
Converse 2/0 19/w 1 19/w 245 Amps 160 Amps
Hunter 2/0 19/w 2/0 19/w 245 Amps 180 Amps
Hollins 3/0 19/w 1/0 19/w 280 Amps 205 Amps
Rockland 3/0 19/w 3/0 19/w 280 Amps 205 Amps
Sweetbriar 4/0 19/w 2/0 19/w 315 Amps 240 Amps
Monmouth 4/0 19/w 4/0 19/w 315 Amps 240 Amps
Pratt 250 37/w 3/0 19/w 345 Amps 265 Amps
Wesleyan 350 37/w 4/0 19/w 415 Amps 320 Amps
Holyoke 500 37/w 300 37/w 495 Amps 395 Amps
Rider 500 37/w 350 37/w 495 Amps 395 Amps
Fairfield 750 61/w 500 37/w 615 Amps 525 Amps