Three Conductor Aluminum Jacketed MC Cable and Grounding Conductor 600V

Check up to five results to perform an action.

Applications
MC Cable is approved for use in many applications including direct burial, use in cable tray and outdoor exposure. The PVC jacket is free of harmful heavy metals in compliance with RoHS, Directive 2002/95/EC.
  • Run from the combiner box to the inverter
  • Suitable for rooftop solar applications
  • Outdoors
  • In wet locations (Type XHHW-2 , or RHW-2 conductors)
  • Direct buried
  • Encased in concrete
  • Hazardous locations
  • Strong, but lightweight alloy armor resists damage
  • Suitable for wet locations, direct burial, encased in concrete and other uses per the NEC
  • More flexible than conduit
  • Factory tested engineered product that protects conductors from damage during installation
  • Meets or exceeds requirements of the NEC, as well as applicable UL Standards.
Specifications
  • Single conductors are rated XHHW-2, and CT Use 1/0 AWG and larger
  • Aluminum armor is rated for Direct Burial, using 6 AWG and larger conductors, with overall jacket
  • Approved for use in certain hazardous locations as permitted in Articles 501, 502, 503 and 504
  • UL 1569, Metal Clad Cables
  • UL 44, Rubber-Insulated wires and cables
  • ICEA S-95-658 Standard for Non-shielded Power Cables Rated 2000 volts or less
Construction
Stranded Aluminum alloy (AA8000) compacted conductor, Class B stranding, per ASTM B 801. Flame retardant thermoset crosslinked polyethylene (XLPE) insulation. Grounding is one bare aluminum alloy (AA-8000)compacted stranded conductor. Phase and grounding conductors are cabled together with binder tape. Aluminum interlocked armor, applied over the binder tape and a longitudinal marker tape, for ID, when un-jacketed. Black sunlight resistant and flame retardant polyvinyl chloride (PVC) compound jacket.

Notes
Data is approximate and subject to normal manufacturing tolerances. For sizes not listed above please contact sales.

The rating of the overcurrent device shown above is in accordance with the NEC® for single runs. See 240.4 and 240.6. Also, see 110.14 and Table 310.15(B)16 of the NEC.






    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 17 of 17 1 

Item #

Conductor
Size
(AWG/KCMIL)

No.
of
Phase
Conductors

Grounding
Conductor
Size
(AWG/KCMIL)

Diameter
of
Conductor
Assembly
Under
Armor
(Inches)

Diameter
of
Cable
Over
Armor
(Inches)

Overall
Finished
Diameter
of
Cable
(Inches)

Cable
Weight
(LBS/MFT)

Rating
of
OC Device
@ 75°C
(AMPS)

Rated
Ampacity
@ 75°C
(AMPS)

A6-03AIA-WG-600V 6 3 6 0.61 0.83 0.93 312 50 50
A4-03AIA-WG-600V 4 3 6 0.68 0.09 1.00 380 70 65
A2-03AIA-WG-600V 2 3 6 0.77 1.00 1.09 482 90 90
A1-03AIA-WG-600V 1 3 4 0.90 1.12 1.22 595 100 100
A1/0-03AIA-WG-600V 1/0 3 4 0.96 1.18 1.28 691 125 120
A2/0-03AIA-WG-600V 2/0 3 4 1.05 1.28 1.38 813 150 135
A3/0-03AIA-WG-600V 3/0 3 4 1.13 1.36 1.46 950 175 155
A4/0-03AIA-WG-600V 4/0 3 2 1.27 1.55 1.67 1176 200 180
A250-03AIA-WG-600V 250 3 2 1.40 1.69 1.81 1381 225 205
A300-03AIA-WG-600V 300 3 2 1.51 1.79 1.91 1570 250 230
A350-03AIA-WG-600V 350 3 2 1.61 1.89 2.01 1755 250 250
A400-03AIA-WG-600V 400 3 1 1.70 1.99 2.11 1919 300 270
A500-03AIA-WG-600V 500 3 1 1.87 2.15 2.72 2269 350 310
A600-03AIA-WG-600V 600 3 1 2.10 2.38 2.53 2766 350 340
A700-03AIA-WG-600V 700 3 1/0 2.24 2.52 2.67 3134 400 375
A750-03AIA-WG-600V 750 3 1/0 2.30 2.59 2.74 3306 400 385
A900-03AIA-WG-600V 900 3 250 2.50 2.78 2.93 3959 450 425