Material
Thermal Resistivity (ρT)
Km/W

IEC 60287

Insulating Materials*
Paper insulation in solid type cables 6.0 6.0
Paper insulation in oil-filled cables 5.0 5.0
Paper insulation in cables with external gas pressure 5.5
Paper insulation in cables with internal gas pressure
A) Pre-impregnated 5.5 5.5
B) Mass-impregnated 6.0
PE 3.5 3.5
XLPE 3.5 3.5
PPL 5.5 5.5
Polyvinyl chloride
Up to and including 3kV cables 5.0
Greater than 3kV cables 6.0
EPR
Up to and including 3kV cables 3.5
Greater than 3kV cables 5.0
Butyl rubber 5.0
Rubber 5.0
Protective Coverings
Compounded jute and fibrous materials 6.0
Rubber sandwich protection 6.0
Polychoroprene
PVC
Up to and including 35kV cables 5.0
Greater than 35kV cables 6.0
PVC/Bitumen on corrugated aluminum sheaths 6.0
PE 3.5 3.5
Materials for Duct Installations
Concrete 1.0
Fibre 4.8
Earthenware 1.2
PVC 6.0
PE 3.5

*For the purposes of current rating calculations, the semiconducting screening materials are assumed to have the same thermal properties as the adjacent dielectric materials.