ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
All Categories > Control Cables & Portable Power Cables > Control Cables > Control Cable/Power Cable FR-XLPE > Control Cable/Power Cable FR-XLPE Insulated Conductors, XLPO Jacket, 600V > Control Cable FR-XLPE Insulated Conductors, Longitudinal Corrugated Bare Copper Shield, Low Smoke Zero Halogen Polyolefin XLPO Jacket, 600V > Control Cable FR-XLPE Insulated Conductors, Longitudinal Corrugated Bare Copper Shield, Low Smoke Zero Halogen Polyolefin XLPO Jacket, 600V > View Items  

Control Cable FR-XLPE Insulated Conductors, Longitudinal Corrugated Bare Copper Shield, Low Smoke Zero Halogen Polyolefin XLPO Jacket, 600V

Check up to five results to perform an action.

Applications

Control or signal cable for important circuits in industrial plants and station control cable for electric utilities where flame resistance is essential. Suitable for the operation and interconnection of protective devices; rated circuit voltage 600 volts; recommended for operation at 90°C maximum continuous conductor temperature in wet or dry locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, and are suitable for direct burial.

Specifications

  • Conductors conform to ASTM B-3 & B-8.
  • Insulation conforms to UL Standard 44.
  • TC Type Tray Cable per Article 340 of the NEC.
  • Cables designed to pass the IEEE-383 & IEEE-1202 tests.
  • Jacket suitable for Sunlight Resistant applications.
  • Cables meet requirements of ICEA S-73-532 and ICEA S-95-658/NEMA WC70.

Construction

Stranded copper conductors, XLP insulated, Method 1 - Table E1 or E2 color coded or Method 4 phase-identified, conductors twisted with suitable fillers, Longitudinal Corrugated Bare Copper Tape Shield, LSZH jacket overall, surface printed.

Options

Also available with -G Ground Wire, -SH Mylar Aluminum Foil Shield, No Shield

Notes

Dimensional data not binding, we reserve the right to alter specifications without notice. SHIPPING TOLERANCE +/- 10%






    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 60 of 60 1 

Item #

Conductor Size
AWG or kcmil

Number
of
Conductors

O.A.
(mils)

O.D.
(mils)

Weight
(lbs/MFT)

18-02XLOHS 18 2 45 0.3 58
18-03XLOHS 18 3 45 0.3 75
18-04XLOHS 18 4 45 0.4 93
18-05XLOHS 18 5 45 0.4 114
18-07XLOHS 18 7 45 0.5 135
18-09XLOHS 18 9 45 0.5 172
18-12XLOHS 18 12 45 0.6 202
18-15XLOHS 18 15 60 0.6 229
18-19XLOHS 18 19 60 0.8 262
18-25XLOHS 18 25 60 0.9 323
18-31XLOHS 18 31 80 0.9 377
18-37XLOHS 18 37 80 1 448
16-02XLOHS 16 2 45 0.4 69
16-03XLOHS 16 3 45 0.4 84
16-04XLOHS 16 4 45 0.4 104
16-05XLOHS 16 5 60 0.4 119
16-07XLOHS 16 7 60 0.5 140
16-09XLOHS 16 9 60 0.6 181
16-12XLOHS 16 12 60 0.6 246
16-15XLOHS 16 15 80 0.7 302
16-19XLOHS 16 19 80 0.7 352
16-25XLOHS 16 25 80 0.8 469
16-31XLOHS 16 31 80 0.9 590
16-37XLOHS 16 37 80 1 675
14-02XLOHS 14 2 45 0.4 88
14-03XLOHS 14 3 45 0.4 109
14-04XLOHS 14 4 45 0.5 134
14-05XLOHS 14 5 45 0.5 155
14-07XLOHS 14 7 45 0.5 210
14-09XLOHS 14 9 60 0.7 296
14-12XLOHS 14 12 60 0.7 353
14-15XLOHS 14 15 60 0.8 450
14-19XLOHS 14 19 60 0.8 529
14-25XLOHS 14 25 80 1 740
14-31XLOHS 14 31 80 1.1 881
14-37XLOHS 14 37 80 1.2 1015
12-02XLOHS 12 2 45 0.5 119
12-03XLOHS 12 3 45 0.5 144
12-04XLOHS 12 4 45 0.5 180
12-05XLOHS 12 5 45 0.6 235
12-07XLOHS 12 7 60 0.6 295
12-09XLOHS 12 9 60 0.7 387
12-12XLOHS 12 12 60 0.8 498
12-15XLOHS 12 15 80 0.9 653
12-19XLOHS 12 19 80 1 759
12-25XLOHS 12 25 80 1.1 1021
12-31XLOHS 12 31 80 1.2 1217
12-37XLOHS 12 37 80 1.3 1413
10-02XLOHS 10 2 45 0.5 169
10-03XLOHS 10 3 45 0.5 205
10-04XLOHS 10 4 60 0.6 275
10-05XLOHS 10 5 60 0.7 331
10-07XLOHS 10 7 60 0.7 422
10-09XLOHS 10 9 60 0.8 537
10-12XLOHS 10 12 80 1 738
10-15XLOHS 10 15 80 1.1 904
10-19XLOHS 10 19 80 1.1 1080
10-25XLOHS 10 25 80 1.3 1431
10-31XLOHS 10 31 80 1.4 1724
10-37XLOHS 10 37 80 1.5 2005