Applications
Construction
Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire: Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hydroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket
Specifications
NOTES:
Item # |
Size
|
Insulation
|
No. of
|
Size
|
Conductor
|
Insulation
|
Insulation
|
Overall
|
Approximate
|
Minimum
|
Ampacity
|
Ampacity
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
A4-03AIAPC5UT105 |
Size AWG or KCMIL N/A 4 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 10 |
Conductor Diameter (in) N/A 0.215 |
Insulation Diameter (in) N/A 0.5 |
Insulation Shield Diameter (in) N/A 0.56 |
Overall Jacket Diameter (in) N/A 1.58 |
Approximate Weight (lb/MFT) N/A 1117 |
Minimum Bending Radius (in) N/A 12 |
Ampacity 105ºC in Duct N/A 86 |
Ampacity 105ºC in Air N/A 90 |
A2-03AIAPC5UT105 |
Size AWG or KCMIL N/A 2 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 10 |
Conductor Diameter (in) N/A 0.266 |
Insulation Diameter (in) N/A 0.55 |
Insulation Shield Diameter (in) N/A 0.61 |
Overall Jacket Diameter (in) N/A 1.71 |
Approximate Weight (lb/MFT) N/A 1321 |
Minimum Bending Radius (in) N/A 12 |
Ampacity 105ºC in Duct N/A 110 |
Ampacity 105ºC in Air N/A 120 |
A1-03AIAPC5UT105 |
Size AWG or KCMIL N/A 1 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 10 |
Conductor Diameter (in) N/A 0.299 |
Insulation Diameter (in) N/A 0.58 |
Insulation Shield Diameter (in) N/A 0.64 |
Overall Jacket Diameter (in) N/A 1.78 |
Approximate Weight (lb/MFT) N/A 1429 |
Minimum Bending Radius (in) N/A 13 |
Ampacity 105ºC in Duct N/A 130 |
Ampacity 105ºC in Air N/A 140 |
A1/0-03AIAPC5UT105 |
Size AWG or KCMIL N/A 1/0 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 10 |
Conductor Diameter (in) N/A 0.336 |
Insulation Diameter (in) N/A 0.62 |
Insulation Shield Diameter (in) N/A 0.68 |
Overall Jacket Diameter (in) N/A 1.88 |
Approximate Weight (lb/MFT) N/A 1619 |
Minimum Bending Radius (in) N/A 14 |
Ampacity 105ºC in Duct N/A 150 |
Ampacity 105ºC in Air N/A 160 |
A2/0-03AIAPC5UT105 |
Size AWG or KCMIL N/A 2/0 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 8 |
Conductor Diameter (in) N/A 0.379 |
Insulation Diameter (in) N/A 0.66 |
Insulation Shield Diameter (in) N/A 0.72 |
Overall Jacket Diameter (in) N/A 1.98 |
Approximate Weight (lb/MFT) N/A 1843 |
Minimum Bending Radius (in) N/A 14 |
Ampacity 105ºC in Duct N/A 170 |
Ampacity 105ºC in Air N/A 185 |
A3/0-03AIAPC5UT105 |
Size AWG or KCMIL N/A 3/0 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 8 |
Conductor Diameter (in) N/A 0.423 |
Insulation Diameter (in) N/A 0.71 |
Insulation Shield Diameter (in) N/A 0.76 |
Overall Jacket Diameter (in) N/A 2.07 |
Approximate Weight (lb/MFT) N/A 2038 |
Minimum Bending Radius (in) N/A 15 |
Ampacity 105ºC in Duct N/A 195 |
Ampacity 105ºC in Air N/A 215 |
A4/0-03AIAPC5UT105 |
Size AWG or KCMIL N/A 4/0 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 8 |
Conductor Diameter (in) N/A 0.479 |
Insulation Diameter (in) N/A 0.76 |
Insulation Shield Diameter (in) N/A 0.82 |
Overall Jacket Diameter (in) N/A 2.19 |
Approximate Weight (lb/MFT) N/A 2280 |
Minimum Bending Radius (in) N/A 16 |
Ampacity 105ºC in Duct N/A 220 |
Ampacity 105ºC in Air N/A 250 |
A250-03AIAPC5UT105 |
Size AWG or KCMIL N/A 250 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 8 |
Conductor Diameter (in) N/A 0.522 |
Insulation Diameter (in) N/A 0.81 |
Insulation Shield Diameter (in) N/A 0.87 |
Overall Jacket Diameter (in) N/A 2.3 |
Approximate Weight (lb/MFT) N/A 2504 |
Minimum Bending Radius (in) N/A 17 |
Ampacity 105ºC in Duct N/A 245 |
Ampacity 105ºC in Air N/A 280 |
A350-03AIAPC5UT105 |
Size AWG or KCMIL N/A 350 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 7 |
Conductor Diameter (in) N/A 0.622 |
Insulation Diameter (in) N/A 0.91 |
Insulation Shield Diameter (in) N/A 0.97 |
Overall Jacket Diameter (in) N/A 2.54 |
Approximate Weight (lb/MFT) N/A 3110 |
Minimum Bending Radius (in) N/A 18 |
Ampacity 105ºC in Duct N/A 310 |
Ampacity 105ºC in Air N/A 345 |
A500-03AIAPC5UT105 |
Size AWG or KCMIL N/A 500 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 6 |
Conductor Diameter (in) N/A 0.742 |
Insulation Diameter (in) N/A 1.03 |
Insulation Shield Diameter (in) N/A 1.1 |
Overall Jacket Diameter (in) N/A 2.84 |
Approximate Weight (lb/MFT) N/A 3937 |
Minimum Bending Radius (in) N/A 20 |
Ampacity 105ºC in Duct N/A 365 |
Ampacity 105ºC in Air N/A 430 |
A750-03AIAPC5UT105 |
Size AWG or KCMIL N/A 750 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 5 |
Conductor Diameter (in) N/A 0.917 |
Insulation Diameter (in) N/A 1.21 |
Insulation Shield Diameter (in) N/A 1.29 |
Overall Jacket Diameter (in) N/A 3.25 |
Approximate Weight (lb/MFT) N/A 5218 |
Minimum Bending Radius (in) N/A 23 |
Ampacity 105ºC in Duct N/A 460 |
Ampacity 105ºC in Air N/A 550 |
A1000-03AIAPC5UT105 |
Size AWG or KCMIL N/A 1000 |
Insulation Thickness (mil) N/A 115 |
No. of Ground Wires N/A 3 |
Size AWG of Ground Wires N/A 4 |
Conductor Diameter (in) N/A 1.071 |
Insulation Diameter (in) N/A 1.37 |
Insulation Shield Diameter (in) N/A 1.44 |
Overall Jacket Diameter (in) N/A 3.59 |
Approximate Weight (lb/MFT) N/A 6429 |
Minimum Bending Radius (in) N/A 26 |
Ampacity 105ºC in Duct N/A 535 |
Ampacity 105ºC in Air N/A 650 |