All Categories > Armored Cables > PowerGuard® Armored 5-35kV Aluminum 3-Conductor with Copper Ground Wire TR-XLPE Insulation Copper Tape Shield Aluminum Interlocked Armor AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 > PowerGuard® Armored 5kV AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 > PowerGuard® Armored 5kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8 > View Items  

PowerGuard® Armored 5kV 100% AL 3/C with CU Ground Wire TR-XLPE Insulation CU Tape Shield AIA PVC Jacket UL Type MV-105 or MC, AEIC CS8

Check up to five results to perform an action.

Applications

  • Armored Medium-Voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods
  • Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart
  • Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete

Construction

Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap
Ground Wire:  Three bare copper ground wires placed at the interstice of the conductor.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Armor: Aluminum Interlocked Armor applied over the binder tape of the cable core
Jacket: Black, sunlight resistant, flame retardant PVC jacket

Specifications

  • AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
  • ICEA S-93-639, 5-46 kV Shielded Power Cable
  • ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
  • UL-1072 MV-105
  • UL-1569, Metal Clad Cables
  • IEEE 383 Flame Test
  • For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
  • UL MC-HL available upon request

NOTES:

  • The above dimensions are approximate and subject to normal manufacturing tolerances.
  • Ampacities are based on the following: Three Phase Operation In Duct (2011 NEC Table 310.60(C)(80): Three-conductor cable in plastic  duct, direct-buried, 105°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited. Isolated  in Air (2011 NEC Table 310.60(C)(72)): Three-conductor cable, 105°C conductor temperature, and 40°C ambient temperature, and shields grounded at one point only. In Cable Tray: per 2011 NEC 392.80(B)(1)(b)3, for single conductor cables, sizes 1/0 AWG and larger, installed in a single layer in an uncovered table tray, with a maintained  space of not less than one cable diameter between individual conductors, the ampacities shall not exceed the allowable ampacities stated in 2011 NEC Table 310.60(C)(72) (Aluminum), “Isolated in Air” values noted above.
  • Insulated  cables are capable of operating at 105°C. However, the maximum operating temperature of the cable should be based on the maximum operating temperature of the cable accessories to be used.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 12 of 12 1 

Item #

Size
AWG
or
KCMIL

Insulation
Thickness
(mil)

No. of
Ground
Wires

Size
AWG
of
Ground
Wires

Conductor
Diameter
(in)

Insulation
Diameter
(in)

Insulation
Shield
Diameter
(in)

Overall
Jacket
Diameter
(in)

Approximate
Weight (lb/MFT)

Minimum
Bending
Radius
(in)

Ampacity
105ºC
in
Duct

Ampacity
105ºC
in
Air

A4-03AIAPC5GT105 4 90 3 10 0.215 0.45 0.51 1.47 1001 11 86 90
A2-03AIAPC5GT105 2 90 3 10 0.266 0.5 0.56 1.58 1165 12 110 120
A1-03AIAPC5GT105 1 90 3 10 0.299 0.53 0.59 1.68 1298 12 130 140
A1/0-03AIAPC5GT105 1/0 90 3 10 0.336 0.57 0.63 1.75 1431 13 150 160
A2/0-03AIAPC5GT105 2/0 90 3 8 0.379 0.61 0.67 1.87 1698 14 170 185
A3/0-03AIAPC5GT105 3/0 90 3 8 0.423 0.66 0.71 1.96 1887 14 195 215
A4/0-03AIAPC5GT105 4/0 90 3 8 0.479 0.71 0.77 2.08 2121 15 220 250
A250-03AIAPC5GT105 250 90 3 8 0.522 0.76 0.82 2.19 2338 16 245 280
A350-03AIAPC5GT105 350 90 3 7 0.622 0.86 0.92 2.44 2927 18 310 345
A500-03AIAPC5GT105 500 90 3 6 0.742 0.98 1.05 2.73 3734 20 365 430
A750-03AIAPC5GT105 750 90 3 5 0.917 1.16 1.24 3.14 4987 23 460 550
A1000-03AIAPC5GT105 1000 90 3 4 1.071 1.32 1.39 3.48 6177 25 535 650