Applications
For installation in tray, trough, conduit, ducts, aerial and direct buried as allowed by the NEC. The cables can be used in main feeder, distribution, and branch circuits for industrial, commercial and electric utility installations. They may operate continuously in wet or dry locations at conductor temperatures not exceeding 105 ºC, at not more than 140 ºC. for emergency overload conditions and 250 ºC during short-circuits. Suitable for systems rated 5 kV/8 kV, 133 % insulation level (grounded systems).

Construction
Copper concentrically stranded compressed conductor; triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; bare copper tape shielded; surface printed black PVC jacket.

Standards
  • National Electrical Code (NEC)
  • UL-1072 MV-105
  • ICEA S-93-639/NEMA WC74
  • ICEA S-97-682
  • AEIC CS8
  • UL listed as Type MV-105 for use in accordance with NEC
  • Sizes 4/0 AWG and larger are listed and marked "Sunlight-Resistant FOR CT USE" in accordance with NEC
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100 % load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC; operating at 105 ºC conductor (NEC Table 310.73).
  • CPE or CSPE Jacket available.
1 - 11 of 11 | Results Per Page | View | Unit of Measure
1 

Item #

Size
AWG or
KCMIL

Stranding

Minimum
Point
Insulation

Minimum
Point
Jacket

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Overall

Net Weight
Per MFT

Ampacity
1/C
in
Cable Tray

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Conduit
In Air

105-115E2 N/A 2 N/A 7 N/A 115 mls N/A 55 mls N/A 0.550 Inches N/A 0.640 Inches N/A 0.840 Inches N/A 510 Lbs N/A N/A 165 Amps N/A 165 Amps
105-115E1 N/A 1 N/A 19 N/A 115 mls N/A 55 mls N/A 0.590 Inches N/A 0.680 Inches N/A 0.880 Inches N/A 620 Lbs N/A N/A 185 Amps N/A 190 Amps
105-115E1/0 N/A 1/0 N/A 19 N/A 115 mls N/A 55 mls N/A 0.640 Inches N/A 0.720 Inches N/A 0.920 Inches N/A 670 Lbs N/A 290 Amps N/A 215 Amps N/A 215 Amps
105-115E2/0 N/A 2/0 N/A 19 N/A 115 mls N/A 70 mls N/A 0.690 Inches N/A 0.770 Inches N/A 0.980 Inches N/A 790 Lbs N/A 335 Amps N/A 245 Amps N/A 255 Amps
105-115E3/0 N/A 3/0 N/A 19 N/A 115 mls N/A 70 mls N/A 0.740 Inches N/A 0.820 Inches N/A 1.030 Inches N/A 920 Lbs N/A 385 Amps N/A 275 Amps N/A 290 Amps
105-115E4/0 N/A 4/0 N/A 19 N/A 115 mls N/A 70 mls N/A 0.800 Inches N/A 0.870 Inches N/A 1.080 Inches N/A 1080 Lbs N/A 445 Amps N/A 315 Amps N/A 330 Amps
105-115E250 N/A 250 N/A 37 N/A 115 mls N/A 70 mls N/A 0.860 Inches N/A 0.930 Inches N/A 1.140 Inches N/A 1230 Lbs N/A 495 Amps N/A 345 Amps N/A 365 Amps
105-115E350 N/A 350 N/A 37 N/A 115 mls N/A 70 mls N/A 0.960 Inches N/A 1.030 Inches N/A 1.240 Inches N/A 1580 Lbs N/A 610 Amps N/A 415 Amps N/A 440 Amps
105-115E500 N/A 500 N/A 37 N/A 115 mls N/A 70 mls N/A 1.080 Inches N/A 1.170 Inches N/A 1.370 Inches N/A 2090 Lbs N/A 765 Amps N/A 500 Amps N/A 535 Amps
105-115E750 N/A 750 N/A 61 N/A 115 mls N/A 70 mls N/A 1.270 Inches N/A 1.360 Inches N/A 1.560 Inches N/A 2950 Lbs N/A 990 Amps N/A 610 Amps N/A 655 Amps
105-115E1000 N/A 1000 N/A 61 N/A 115 mls N/A 70 mls N/A 1.420 Inches N/A 1.510 Inches N/A 1.710 Inches N/A 3910 Lbs N/A 1185 Amps N/A 690 Amps N/A 755 Amps
1 - 11 of 11 | Results Per Page | View | Unit of Measure