Applications
For installation in tray, trough, conduit, ducts, aerial and direct buried as allowed by the NEC. The cables can be used in main feeder, distribution, and branch circuits for industrial, commercial and electric utility installations. They may operate continuously in wet or dry locations at conductor temperatures not exceeding 105 ºC, at not more than 140 ºC for emergency overload conditions and 250 ºC during short-circuits. Suitable for systems rated 35 kV, 133 % & 100 % insulation level (grounded systems).

Construction
Copper concentrically stranded compressed conductor; triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; bare copper tape shielded; surface printed black PVC jacket.

Standards
  • National Electrical Code (NEC)
  • UL-1072 MV-105
  • ICEA S-93-639/NEMA WC74
  • ICEA S-97-682
  • AEIC CS8
  • UL listed as Type MV-105 for use in accordance with NEC
  • Sizes 4/0 AWG and larger are listed and marked ""Sunlight-Resistant FOR CT USE"" in accordance with NEC
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100 % load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC; operating at 105 ºC conductor (NEC Table 310.73).
1 - 9 of 9 | Results Per Page | View | Unit of Measure
1 

Item #

Size
AWG or
KCMIL

Stranding

Minimum
Point
Insulation

Minimum
Point
Jacket

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Overall

Net Weight
Per MFT

Ampacity
1/C
in
Cable Tray

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Conduit
In Air

105-345E1/0 N/A 1/0 N/A 19 N/A 345 mls N/A 70 mls N/A 1.110 Inches N/A 1.200 Inches N/A 1.390 Inches N/A 1180 Lbs N/A N/A 215 Amps N/A 215 Amps
105-345E2/0 N/A 2/0 N/A 19 N/A 345 mls N/A 70 mls N/A 1.150 Inches N/A 1.250 Inches N/A 1.440 Inches N/A 1300 Lbs N/A N/A 245 Amps N/A 255 Amps
105-345E3/0 N/A 3/0 N/A 19 N/A 345 mls N/A 70 mls N/A 1.200 Inches N/A 1.290 Inches N/A 1.490 Inches N/A 1460 Lbs N/A N/A 275 Amps N/A 290 Amps
105-345E4/0 N/A 4/0 N/A 19 N/A 345 mls N/A 70 mls N/A 1.260 Inches N/A 1.340 Inches N/A 1.550 Inches N/A 1650 Lbs N/A 445 Amps N/A 315 Amps N/A 330 Amps
105-345E250 N/A 250 N/A 37 N/A 345 mls N/A 70 mls N/A 1.330 Inches N/A 1.420 Inches N/A 1.600 Inches N/A 1830 Lbs N/A 495 Amps N/A 345 Amps N/A 365 Amps
105-345E350 N/A 350 N/A 37 N/A 345 mls N/A 100 mls N/A 1.430 Inches N/A 1.520 Inches N/A 1.780 Inches N/A 2230 Lbs N/A 610 Amps N/A 415 Amps N/A 440 Amps
105-345E500 N/A 500 N/A 37 N/A 345 mls N/A 100 mls N/A 1.550 Inches N/A 1.660 Inches N/A 1.910 Inches N/A 2930 Lbs N/A 765 Amps N/A 500 Amps N/A 535 Amps
105-345E750 N/A 750 N/A 61 N/A 345 mls N/A 100 mls N/A 1.740 Inches N/A 1.860 Inches N/A 2.120 Inches N/A 3960 Lbs N/A 990 Amps N/A 610 Amps N/A 655 Amps
105-345E1000 N/A 1000 N/A 61 N/A 345 mls N/A 100 mls N/A 1.890 Inches N/A 2.020 Inches N/A 2.270 Inches N/A 4920 Lbs N/A 1185 Amps N/A 690 Amps N/A 755 Amps