Applications
For installation in tray, trough, conduit, ducts, aerial and direct buried as allowed by the NEC. The cables can be used in main feeder, distribution, and branch circuits for industrial, commercial and electric utility installations. They may operate continuously in wet or dry locations at conductor temperatures not exceeding 105 ºC, at not more than 140 ºC. for emergency overload conditions and 250 ºC during short-circuits. Suitable for systems rated 15 kV, 133 % & 100 % insulation level (grounded systems).

Construction
Copper concentrically stranded compressed conductor; triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; bare copper tape shielded; surface printed black PVC jacket.

Standards
  • National Electrical Code (NEC)
  • UL-1072 MV-105
  • ICEA S-93-639/NEMA WC74
  • ICEA S-97-682
  • AEIC CS8
  • UL listed as Type MV-105 for use in accordance with NEC
  • Sizes 4/0 AWG and larger are listed and marked ""Sunlight-Resistant FOR CT USE"" in accordance with NEC
Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105 ºC conductor, at an ambient temperature of 40 ºC.
  • Buried Duct: Three cables per duct operating at 105 ºC conductor, 20 ºC ground ambient, earth ρ = 90, 100 % load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40 ºC; operating at 105 ºC conductor (NEC Table 310.73).
  • CPE or CSPE Jacket available.
1 - 10 of 10 | Results Per Page | View | Unit of Measure
1 

Item #

Size
AWG or
KCMIL

Stranding

Insulation
Thickness
(mls)

Jacket
Thickness
(mils)

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Overall

Net Weight
Per MFT

Ampacity
1/C
in
Cable Tray

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Conduit
In Air

105-220E2 N/A 2 N/A 7 N/A 220 N/A 70 N/A 0.790 Inches N/A 0.860 Inches N/A 1.080 Inches N/A 700 Lbs N/A - Amps N/A 165 Amps N/A 165 Amps
105-220E1/0 N/A 1/0 N/A 19 N/A 220 N/A 70 N/A 0.870 Inches N/A 0.920 Inches N/A 1.140 Inches N/A 870 Lbs N/A 290 Amps N/A 215 Amps N/A 215 Amps
105-220E2/0 N/A 2/0 N/A 19 N/A 220 N/A 70 N/A 0.910 Inches N/A 0.910 Inches N/A 1.180 Inches N/A 930 Lbs N/A 335 Amps N/A 245 Amps N/A 255 Amps
105-220E3/0 N/A 3/0 N/A 19 N/A 220 N/A 70 N/A 0.960 Inches N/A 1.010 Inches N/A 1.230 Inches N/A 1070 Lbs N/A 385 Amps N/A 275 Amps N/A 290 Amps
105-220E4/0 N/A 4/0 N/A 19 N/A 220 N/A 70 N/A 1.020 Inches N/A 1.080 Inches N/A 1.290 Inches N/A 1250 Lbs N/A 445 Amps N/A 315 Amps N/A 330 Amps
105-220E250 N/A 250 N/A 37 N/A 220 N/A 70 N/A 1.080 Inches N/A 1.140 Inches N/A 1.350 Inches N/A 1420 Lbs N/A 495 Amps N/A 345 Amps N/A 365 Amps
105-220E350 N/A 350 N/A 37 N/A 220 N/A 70 N/A 1.180 Inches N/A 1.240 Inches N/A 1.470 Inches N/A 1800 Lbs N/A 610 Amps N/A 415 Amps N/A 440 Amps
105-220E500 N/A 500 N/A 37 N/A 220 N/A 70 N/A 1.310 Inches N/A 1.370 Inches N/A 1.600 Inches N/A 2360 Lbs N/A 756 Amps N/A 500 Amps N/A 535 Amps
105-220E750 N/A 750 N/A 61 N/A 220 N/A 100 N/A 1.500 Inches N/A 1.560 Inches N/A 1.790 Inches N/A 3360 Lbs N/A 990 Amps N/A 610 Amps N/A 655 Amps
105-220E1000 N/A 1000 N/A 61 N/A 220 N/A 100 N/A 1.650 Inches N/A 1.730 Inches N/A 2.020 Inches N/A 4290 Lbs N/A 1185 Amps N/A 690 Amps N/A 755 Amps