Applications
Type MC Cable is primarily used for services, feeders, and branch circuits as specified in the 2011 National Electric Code. Type MC cable with Type XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C. Used for power and lighting indoors, exposed or concealed, in cable tray where identified for such use; in a raceway, or in dry locations and embedded in plaster or against other masonry. Voltage rating for XHHW-2 conductors is 600V.
Construction
Compact stranded AA-8000 series aluminum conductor material per ASTM B800, ASTM B801, ASTM B836, ASTM B901 (Single Input Wire), as applicable. XLPE insulated XHHW-2 conductors are twisted with a bare conductor. A binder tape is wrapped over the conductors with interlocked aluminum tape applied over the assembly. Rated 90°C wet or dry and is flame and sunlight resistant.
Specifications
Type MC cable with Type XHHW-2 conductors are manufactured and tested in accordance with the latest revisions of:
- UL 44 for Thermoset-Insulated Wires and Cables
- UL 83 for Thermoplastic-Insulated Wires and Cables
- UL 1479 Standard for Fire Tests of Through-Penetration Firestops.
- UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
- UL 1569 for Metal-Clad Cables.
- IEEE 1202 - Flame Testing of Cables for Use in Cable Tray, in Industrial and Commercial Occupancies (70,000 BTU/hr).
- ICEA T-29-520 - Vertical Cable Tray Flame Tests (210,000 Btu/hr).
- ICEA S-66-524 and requirements of the National Electric Code
- ICEA S-95-658 (NEMA WC 70) construction requirements
- Federal Specification J-C-30B
Color Code
Three Phase Conductors (3): Black, red, white
Ground Conductor (1): Bare
Other colors and stripes available by special order.
For Special Order
- The entire assembly can be covered with a PVC or CPE outer jacket (black or color). Jacketed MC Cable may be used in wet locations, either direct burial, in underground conduit, or overhead.
- Halogen free jackets are available upon request
- A black jacket (on individual conductors) with color stripes can be requested.
- Bare Ground conductor available upon request.
- For sizes not listed above please contact sales.
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Item # |
Size
|
Phase
|
Number
|
Diameter
|
Thickness
|
Size
|
Diameter
|
Thickness
|
Cabling
|
Overall
|
AL
|
Cable
|
---|---|---|---|---|---|---|---|---|---|---|---|---|
A400-03MC300 |
Size of Cable N/A 400-400-400+300 |
Phase Conductor Size AWG/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1874 |
Overall Diameter of Cable Over Armour (mils) N/A 2198 |
AL Weight (lb/mft) N/A 1749 |
Cable Weight (lb/mft) N/A 2047 |
A400-03MC350 |
Size of Cable N/A 400-400-400+350 |
Phase Conductor Size AWG/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1800 |
Cable Weight (lb/mft) N/A 2103 |
A400-03MC400 |
Size of Cable N/A 400-400-400+400 |
Phase Conductor Size AWG/MCM N/A 400 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 657 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1848 |
Cable Weight (lb/mft) N/A 2154 |
A450-03MC1 |
Size of Cable N/A 450-450-450+1 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1827 |
Overall Diameter of Cable Over Armour (mils) N/A 2150 |
AL Weight (lb/mft) N/A 1677 |
Cable Weight (lb/mft) N/A 1954 |
A450-03MC1/0 |
Size of Cable N/A 450-450-450+1/0 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1870 |
Overall Diameter of Cable Over Armour (mils) N/A 2194 |
AL Weight (lb/mft) N/A 1706 |
Cable Weight (lb/mft) N/A 1986 |
A450-03MC2/0 |
Size of Cable N/A 450-450-450+2/0 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1870 |
Overall Diameter of Cable Over Armour (mils) N/A 2194 |
AL Weight (lb/mft) N/A 1731 |
Cable Weight (lb/mft) N/A 2014 |
A450-03MC3/0 |
Size of Cable N/A 450-450-450+3/0 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1913 |
Overall Diameter of Cable Over Armour (mils) N/A 2237 |
AL Weight (lb/mft) N/A 1771 |
Cable Weight (lb/mft) N/A 2059 |
A450-03MC4/0 |
Size of Cable N/A 450-450-450+4/0 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1953 |
Overall Diameter of Cable Over Armour (mils) N/A 2276 |
AL Weight (lb/mft) N/A 1818 |
Cable Weight (lb/mft) N/A 2111 |
A450-03MC250 |
Size of Cable N/A 450-450-450+250 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1953 |
Overall Diameter of Cable Over Armour (mils) N/A 2276 |
AL Weight (lb/mft) N/A 1855 |
Cable Weight (lb/mft) N/A 2161 |
A450-03MC300 |
Size of Cable N/A 450-450-450+300 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1976 |
Overall Diameter of Cable Over Armour (mils) N/A 2300 |
AL Weight (lb/mft) N/A 1904 |
Cable Weight (lb/mft) N/A 2216 |
A450-03MC350 |
Size of Cable N/A 450-450-450+350 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 1976 |
Overall Diameter of Cable Over Armour (mils) N/A 2300 |
AL Weight (lb/mft) N/A 1950 |
Cable Weight (lb/mft) N/A 2266 |
A450-03MC400 |
Size of Cable N/A 450-450-450+400 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2012 |
Overall Diameter of Cable Over Armour (mils) N/A 2335 |
AL Weight (lb/mft) N/A 2004 |
Cable Weight (lb/mft) N/A 2324 |
A450-03MC450 |
Size of Cable N/A 450-450-450+450 |
Phase Conductor Size AWG/MCM N/A 450 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 701 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2012 |
Overall Diameter of Cable Over Armour (mils) N/A 2335 |
AL Weight (lb/mft) N/A 2049 |
Cable Weight (lb/mft) N/A 2374 |
A500-03MC1 |
Size of Cable N/A 500-500-500+1 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1906 |
Overall Diameter of Cable Over Armour (mils) N/A 2229 |
AL Weight (lb/mft) N/A 1828 |
Cable Weight (lb/mft) N/A 2116 |
A500-03MC1/0 |
Size of Cable N/A 500-500-500+1/0 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1949 |
Overall Diameter of Cable Over Armour (mils) N/A 2272 |
AL Weight (lb/mft) N/A 1857 |
Cable Weight (lb/mft) N/A 2148 |
A500-03MC2/0 |
Size of Cable N/A 500-500-500+2/0 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1949 |
Overall Diameter of Cable Over Armour (mils) N/A 2272 |
AL Weight (lb/mft) N/A 1882 |
Cable Weight (lb/mft) N/A 2177 |
A500-03MC3/0 |
Size of Cable N/A 500-500-500+3/0 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1992 |
Overall Diameter of Cable Over Armour (mils) N/A 2316 |
AL Weight (lb/mft) N/A 1922 |
Cable Weight (lb/mft) N/A 2221 |
A500-03MC4/0 |
Size of Cable N/A 500-500-500+4/0 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 1992 |
Overall Diameter of Cable Over Armour (mils) N/A 2316 |
AL Weight (lb/mft) N/A 1962 |
Cable Weight (lb/mft) N/A 2266 |
A500-03MC250 |
Size of Cable N/A 500-500-500+250 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2035 |
Overall Diameter of Cable Over Armour (mils) N/A 2359 |
AL Weight (lb/mft) N/A 2006 |
Cable Weight (lb/mft) N/A 2324 |
A500-03MC300 |
Size of Cable N/A 500-500-500+300 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2063 |
Overall Diameter of Cable Over Armour (mils) N/A 2387 |
AL Weight (lb/mft) N/A 2057 |
Cable Weight (lb/mft) N/A 2380 |
A500-03MC350 |
Size of Cable N/A 500-500-500+350 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2063 |
Overall Diameter of Cable Over Armour (mils) N/A 2387 |
AL Weight (lb/mft) N/A 2102 |
Cable Weight (lb/mft) N/A 2430 |
A500-03MC400 |
Size of Cable N/A 500-500-500+400 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2155 |
Cable Weight (lb/mft) N/A 2487 |
A500-03MC450 |
Size of Cable N/A 500-500-500+450 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2201 |
Cable Weight (lb/mft) N/A 2537 |
A500-03MC500 |
Size of Cable N/A 500-500-500+500 |
Phase Conductor Size AWG/MCM N/A 500 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 736 |
Thickness of Conductor Insulation (mils) N/A 65 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2094 |
Overall Diameter of Cable Over Armour (mils) N/A 2418 |
AL Weight (lb/mft) N/A 2246 |
Cable Weight (lb/mft) N/A 2586 |
A600-03MC1 |
Size of Cable N/A 600-600-600+1 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2106 |
Overall Diameter of Cable Over Armour (mils) N/A 2430 |
AL Weight (lb/mft) N/A 2144 |
Cable Weight (lb/mft) N/A 2524 |
A600-03MC1/0 |
Size of Cable N/A 600-600-600+1/0 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2106 |
Overall Diameter of Cable Over Armour (mils) N/A 2430 |
AL Weight (lb/mft) N/A 2164 |
Cable Weight (lb/mft) N/A 2547 |
A600-03MC2/0 |
Size of Cable N/A 600-600-600+2/0 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2146 |
Overall Diameter of Cable Over Armour (mils) N/A 2469 |
AL Weight (lb/mft) N/A 2197 |
Cable Weight (lb/mft) N/A 2583 |
A600-03MC3/0 |
Size of Cable N/A 600-600-600+3/0 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2193 |
Overall Diameter of Cable Over Armour (mils) N/A 2517 |
AL Weight (lb/mft) N/A 2238 |
Cable Weight (lb/mft) N/A 2629 |
A600-03MC4/0 |
Size of Cable N/A 600-600-600+4/0 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2287 |
Cable Weight (lb/mft) N/A 2683 |
A600-03MC250 |
Size of Cable N/A 600-600-600+250 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2323 |
Cable Weight (lb/mft) N/A 2733 |
A600-03MC300 |
Size of Cable N/A 600-600-600+300 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2291 |
Overall Diameter of Cable Over Armour (mils) N/A 2615 |
AL Weight (lb/mft) N/A 2378 |
Cable Weight (lb/mft) N/A 2793 |
A600-03MC350 |
Size of Cable N/A 600-600-600+350 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2291 |
Overall Diameter of Cable Over Armour (mils) N/A 2615 |
AL Weight (lb/mft) N/A 2423 |
Cable Weight (lb/mft) N/A 2842 |
A600-03MC400 |
Size of Cable N/A 600-600-600+400 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2476 |
Cable Weight (lb/mft) N/A 2900 |
A600-03MC450 |
Size of Cable N/A 600-600-600+450 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2521 |
Cable Weight (lb/mft) N/A 2950 |
A600-03MC500 |
Size of Cable N/A 600-600-600+500 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2323 |
Overall Diameter of Cable Over Armour (mils) N/A 2646 |
AL Weight (lb/mft) N/A 2567 |
Cable Weight (lb/mft) N/A 2999 |
A600-03MC600 |
Size of Cable N/A 600-600-600+600 |
Phase Conductor Size AWG/MCM N/A 600 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 815 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2666 |
Cable Weight (lb/mft) N/A 3129 |
A650-03MC1 |
Size of Cable N/A 650-650-650+1 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2165 |
Overall Diameter of Cable Over Armour (mils) N/A 2489 |
AL Weight (lb/mft) N/A 2291 |
Cable Weight (lb/mft) N/A 2682 |
A650-03MC1/0 |
Size of Cable N/A 650-650-650+1/0 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2165 |
Overall Diameter of Cable Over Armour (mils) N/A 2489 |
AL Weight (lb/mft) N/A 2311 |
Cable Weight (lb/mft) N/A 2705 |
A650-03MC2/0 |
Size of Cable N/A 650-650-650+2/0 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2209 |
Overall Diameter of Cable Over Armour (mils) N/A 2532 |
AL Weight (lb/mft) N/A 2345 |
Cable Weight (lb/mft) N/A 2742 |
A650-03MC3/0 |
Size of Cable N/A 650-650-650+3/0 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2256 |
Overall Diameter of Cable Over Armour (mils) N/A 2580 |
AL Weight (lb/mft) N/A 2386 |
Cable Weight (lb/mft) N/A 2787 |
A650-03MC4/0 |
Size of Cable N/A 650-650-650+4/0 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2256 |
Overall Diameter of Cable Over Armour (mils) N/A 2580 |
AL Weight (lb/mft) N/A 2425 |
Cable Weight (lb/mft) N/A 2832 |
A650-03MC250 |
Size of Cable N/A 650-650-650+250 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2471 |
Cable Weight (lb/mft) N/A 2892 |
A650-03MC300 |
Size of Cable N/A 650-650-650+300 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2517 |
Cable Weight (lb/mft) N/A 2942 |
A650-03MC350 |
Size of Cable N/A 650-650-650+350 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2572 |
Cable Weight (lb/mft) N/A 3002 |
A650-03MC400 |
Size of Cable N/A 650-650-650+400 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2358 |
Overall Diameter of Cable Over Armour (mils) N/A 2682 |
AL Weight (lb/mft) N/A 2619 |
Cable Weight (lb/mft) N/A 3054 |
A650-03MC450 |
Size of Cable N/A 650-650-650+450 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2386 |
Overall Diameter of Cable Over Armour (mils) N/A 2709 |
AL Weight (lb/mft) N/A 2669 |
Cable Weight (lb/mft) N/A 3109 |
A650-03MC500 |
Size of Cable N/A 650-650-650+500 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2386 |
Overall Diameter of Cable Over Armour (mils) N/A 2709 |
AL Weight (lb/mft) N/A 2715 |
Cable Weight (lb/mft) N/A 3158 |
A650-03MC600 |
Size of Cable N/A 650-650-650+600 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2429 |
Overall Diameter of Cable Over Armour (mils) N/A 2753 |
AL Weight (lb/mft) N/A 2816 |
Cable Weight (lb/mft) N/A 3289 |
A650-03MC650 |
Size of Cable N/A 650-650-650+650 |
Phase Conductor Size AWG/MCM N/A 650 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 843 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 650 |
Diameter of Ground (mils) N/A 843 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2429 |
Overall Diameter of Cable Over Armour (mils) N/A 2753 |
AL Weight (lb/mft) N/A 2861 |
Cable Weight (lb/mft) N/A 3338 |
A700-03MC1 |
Size of Cable N/A 700-700-700+1 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1 |
Diameter of Ground (mils) N/A 299 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2448 |
Cable Weight (lb/mft) N/A 2852 |
A700-03MC1/0 |
Size of Cable N/A 700-700-700+1/0 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2468 |
Cable Weight (lb/mft) N/A 2875 |
A700-03MC2/0 |
Size of Cable N/A 700-700-700+2/0 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2244 |
Overall Diameter of Cable Over Armour (mils) N/A 2568 |
AL Weight (lb/mft) N/A 2493 |
Cable Weight (lb/mft) N/A 2904 |
A700-03MC3/0 |
Size of Cable N/A 700-700-700+3/0 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2335 |
Overall Diameter of Cable Over Armour (mils) N/A 2658 |
AL Weight (lb/mft) N/A 2542 |
Cable Weight (lb/mft) N/A 2957 |
A700-03MC4/0 |
Size of Cable N/A 700-700-700+4/0 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2335 |
Overall Diameter of Cable Over Armour (mils) N/A 2658 |
AL Weight (lb/mft) N/A 2582 |
Cable Weight (lb/mft) N/A 3002 |
A700-03MC250 |
Size of Cable N/A 700-700-700+250 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2390 |
Overall Diameter of Cable Over Armour (mils) N/A 2713 |
AL Weight (lb/mft) N/A 2628 |
Cable Weight (lb/mft) N/A 3063 |
A700-03MC300 |
Size of Cable N/A 700-700-700+300 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2390 |
Overall Diameter of Cable Over Armour (mils) N/A 2713 |
AL Weight (lb/mft) N/A 2674 |
Cable Weight (lb/mft) N/A 3113 |
A700-03MC350 |
Size of Cable N/A 700-700-700+350 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2441 |
Overall Diameter of Cable Over Armour (mils) N/A 2765 |
AL Weight (lb/mft) N/A 2729 |
Cable Weight (lb/mft) N/A 3173 |
A700-03MC400 |
Size of Cable N/A 700-700-700+400 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2441 |
Overall Diameter of Cable Over Armour (mils) N/A 2765 |
AL Weight (lb/mft) N/A 2776 |
Cable Weight (lb/mft) N/A 3225 |
A700-03MC450 |
Size of Cable N/A 700-700-700+450 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2472 |
Overall Diameter of Cable Over Armour (mils) N/A 2796 |
AL Weight (lb/mft) N/A 2827 |
Cable Weight (lb/mft) N/A 3280 |
A700-03MC500 |
Size of Cable N/A 700-700-700+500 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2472 |
Overall Diameter of Cable Over Armour (mils) N/A 2796 |
AL Weight (lb/mft) N/A 2873 |
Cable Weight (lb/mft) N/A 3329 |
A700-03MC600 |
Size of Cable N/A 700-700-700+600 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2973 |
Cable Weight (lb/mft) N/A 3460 |
A700-03MC700 |
Size of Cable N/A 700-700-700+700 |
Phase Conductor Size AWG/MCM N/A 700 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 878 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 3065 |
Cable Weight (lb/mft) N/A 3560 |
A750-03MC1/0 |
Size of Cable N/A 750-750-750+1/0 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2616 |
Cable Weight (lb/mft) N/A 3036 |
A750-03MC2/0 |
Size of Cable N/A 750-750-750+2/0 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2307 |
Overall Diameter of Cable Over Armour (mils) N/A 2631 |
AL Weight (lb/mft) N/A 2641 |
Cable Weight (lb/mft) N/A 3064 |
A750-03MC3/0 |
Size of Cable N/A 750-750-750+3/0 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2350 |
Overall Diameter of Cable Over Armour (mils) N/A 2674 |
AL Weight (lb/mft) N/A 2681 |
Cable Weight (lb/mft) N/A 3108 |
A750-03MC4/0 |
Size of Cable N/A 750-750-750+4/0 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2406 |
Overall Diameter of Cable Over Armour (mils) N/A 2729 |
AL Weight (lb/mft) N/A 2731 |
Cable Weight (lb/mft) N/A 3164 |
A750-03MC250 |
Size of Cable N/A 750-750-750+250 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2777 |
Cable Weight (lb/mft) N/A 3224 |
A750-03MC300 |
Size of Cable N/A 750-750-750+300 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2822 |
Cable Weight (lb/mft) N/A 3274 |
A750-03MC350 |
Size of Cable N/A 750-750-750+350 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2457 |
Overall Diameter of Cable Over Armour (mils) N/A 2780 |
AL Weight (lb/mft) N/A 2868 |
Cable Weight (lb/mft) N/A 3324 |
A750-03MC400 |
Size of Cable N/A 750-750-750+400 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2925 |
Cable Weight (lb/mft) N/A 3386 |
A750-03MC450 |
Size of Cable N/A 750-750-750+450 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2512 |
Overall Diameter of Cable Over Armour (mils) N/A 2835 |
AL Weight (lb/mft) N/A 2971 |
Cable Weight (lb/mft) N/A 3436 |
A750-03MC500 |
Size of Cable N/A 750-750-750+500 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2543 |
Overall Diameter of Cable Over Armour (mils) N/A 2867 |
AL Weight (lb/mft) N/A 3022 |
Cable Weight (lb/mft) N/A 3491 |
A750-03MC600 |
Size of Cable N/A 750-750-750+600 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3123 |
Cable Weight (lb/mft) N/A 3622 |
A750-03MC700 |
Size of Cable N/A 750-750-750+700 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3215 |
Cable Weight (lb/mft) N/A 3723 |
A750-03MC750 |
Size of Cable N/A 750-750-750+750 |
Phase Conductor Size AWG/MCM N/A 750 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 909 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2587 |
Overall Diameter of Cable Over Armour (mils) N/A 2910 |
AL Weight (lb/mft) N/A 3261 |
Cable Weight (lb/mft) N/A 3772 |
A12-03MC12 |
Size of Cable N/A 12-12-12+12 |
Phase Conductor Size AWG/MCM N/A 12 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 91 |
Thickness of Conductor Insulation (mils) N/A 30 |
Size of Ground Conductor AWG/MCM N/A 12 |
Diameter of Ground (mils) N/A 91 |
Thickness of Ground Insulation (mils) N/A 30 |
Cabling Diameter (mils) N/A 366 |
Overall Diameter of Cable Over Armour (mils) N/A 640 |
AL Weight (lb/mft) N/A 93 |
Cable Weight (lb/mft) N/A 119 |
A800-03MC1/0 |
Size of Cable N/A 800-800-800+1/0 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 1/2000 |
Diameter of Ground (mils) N/A 336 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2370 |
Overall Diameter of Cable Over Armour (mils) N/A 2694 |
AL Weight (lb/mft) N/A 2764 |
Cable Weight (lb/mft) N/A 3194 |
A800-03MC2/0 |
Size of Cable N/A 800-800-800+2/0 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 2/2000 |
Diameter of Ground (mils) N/A 376 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2370 |
Overall Diameter of Cable Over Armour (mils) N/A 2694 |
AL Weight (lb/mft) N/A 2789 |
Cable Weight (lb/mft) N/A 3223 |
A800-03MC3/0 |
Size of Cable N/A 800-800-800+3/0 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 3/2000 |
Diameter of Ground (mils) N/A 421 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2413 |
Overall Diameter of Cable Over Armour (mils) N/A 2737 |
AL Weight (lb/mft) N/A 2829 |
Cable Weight (lb/mft) N/A 3267 |
A800-03MC4/0 |
Size of Cable N/A 800-800-800+4/0 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 4/2000 |
Diameter of Ground (mils) N/A 476 |
Thickness of Ground Insulation (mils) N/A 55 |
Cabling Diameter (mils) N/A 2469 |
Overall Diameter of Cable Over Armour (mils) N/A 2792 |
AL Weight (lb/mft) N/A 2879 |
Cable Weight (lb/mft) N/A 3323 |
A800-03MC250 |
Size of Cable N/A 800-800-800+250 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 250 |
Diameter of Ground (mils) N/A 520 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2469 |
Overall Diameter of Cable Over Armour (mils) N/A 2792 |
AL Weight (lb/mft) N/A 2916 |
Cable Weight (lb/mft) N/A 3372 |
A800-03MC300 |
Size of Cable N/A 800-800-800+300 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 300 |
Diameter of Ground (mils) N/A 571 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2524 |
Overall Diameter of Cable Over Armour (mils) N/A 2847 |
AL Weight (lb/mft) N/A 2971 |
Cable Weight (lb/mft) N/A 3434 |
A800-03MC350 |
Size of Cable N/A 800-800-800+350 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 350 |
Diameter of Ground (mils) N/A 614 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2524 |
Overall Diameter of Cable Over Armour (mils) N/A 2847 |
AL Weight (lb/mft) N/A 3017 |
Cable Weight (lb/mft) N/A 3483 |
A800-03MC400 |
Size of Cable N/A 800-800-800+400 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 400 |
Diameter of Ground (mils) N/A 657 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3074 |
Cable Weight (lb/mft) N/A 3546 |
A800-03MC450 |
Size of Cable N/A 800-800-800+450 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 450 |
Diameter of Ground (mils) N/A 701 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3120 |
Cable Weight (lb/mft) N/A 3595 |
A800-03MC500 |
Size of Cable N/A 800-800-800+500 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 500 |
Diameter of Ground (mils) N/A 736 |
Thickness of Ground Insulation (mils) N/A 65 |
Cabling Diameter (mils) N/A 2579 |
Overall Diameter of Cable Over Armour (mils) N/A 2902 |
AL Weight (lb/mft) N/A 3165 |
Cable Weight (lb/mft) N/A 3644 |
A800-03MC600 |
Size of Cable N/A 800-800-800+600 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 600 |
Diameter of Ground (mils) N/A 815 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2610 |
Overall Diameter of Cable Over Armour (mils) N/A 2934 |
AL Weight (lb/mft) N/A 3264 |
Cable Weight (lb/mft) N/A 3773 |
A800-03MC700 |
Size of Cable N/A 800-800-800+700 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 700 |
Diameter of Ground (mils) N/A 878 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3364 |
Cable Weight (lb/mft) N/A 3882 |
A800-03MC750 |
Size of Cable N/A 800-800-800+750 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 750 |
Diameter of Ground (mils) N/A 909 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3410 |
Cable Weight (lb/mft) N/A 3931 |
A800-03MC800 |
Size of Cable N/A 800-800-800+800 |
Phase Conductor Size AWG/MCM N/A 800 |
Number of Phase Conductors N/A 3 |
Diameter of Conductor (mils) N/A 937 |
Thickness of Conductor Insulation (mils) N/A 80 |
Size of Ground Conductor AWG/MCM N/A 800 |
Diameter of Ground (mils) N/A 937 |
Thickness of Ground Insulation (mils) N/A 80 |
Cabling Diameter (mils) N/A 2654 |
Overall Diameter of Cable Over Armour (mils) N/A 2977 |
AL Weight (lb/mft) N/A 3455 |
Cable Weight (lb/mft) N/A 3980 |