ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION

Applications
Paralleled conductors are sunlight-resistant,photovoltaic wire rated 90°C wet or dry, 2000 volts for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31(A) and other applicable parts of the National Electrical Code (NEC), NFPA 70.

• For use in free air, raceways or direct burial in accordance with NEC.

Construction
Conductor: 8 AWG thru 1000 kcmil compact aluminum ACM (8000 series) conductors. Insulation is Flame-Retardant Cross-Linked Polyethylene (XLPE), black, suitable for 2000 V.
Print Legend: AWG (PLANT OF MFG) SUNGUARD ™ 2000 V PV WIRE OR RHH OR RHW-2 OR 600 V USE-2 (SIZE) AL ACM 90°C WET OR DRY SUN RES (UL) -40 ºC c(UL) VW-1 RWU90 1000 V DIR BUR MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK
Paralleling: One phase conductor is black with red stripes, the other conductor is white with red stripes. Conductors are pre-installed together on reel.

Features

  • Rated 90ºC wet and dry
  • Deformation-resistant at high temperatures
  • Excellent moisture resistance, exceeds UL 44
  • Stable electrical properties over a broad temperature range
  • Excellent resistance to crush and compression cuts
  • Resistant to most oils and chemicals
  • UV/sunlight-resistant
  • Meets cold bend test at -40ºC
  • Use Parallel SunGard to avoid mismatch of Positive and Negative sets
  • Reduce labor costs and equipment cost for laying cable in trench by deploying one reel, instead of two

Standards

  • Rated 90°C wet and dry
  • Deformation-resistant at high temperatures
  • Excellent moisture resistance, exceeds UL 44
  • Stable electrical properties over a broad temperature range
  • Excellent resistance to crush and compression cuts
  • Resistant to most oils and chemicals
  • UV/sunlight-resistant
  • Meets cold bend test at -40ºC
  • VW-1 Rating upon available upon request


Note
Material cut to length and shipped on non-returnable wood or steel reels

Option
UL 1581 VW-1 compliance available on request

1 - 17 of 17 | Results Per Page | View |
1 

Item #

Conductor
Size
(AWG/kcmil)

Conductor
Stranding

Nominal
Conductor
O.D.
inches

Minimum
Average
Insulation
Thickness
inches

Duplexed
Cable
Diameter
inches

Aluminum
Weight
lbs/MFT

Net Cable
Weight
lbs/MFT

A8-02PV2X0700* N/A 8 N/A 7/.0486 N/A 0.134 N/A 0.085 N/A .62 N/A 32 N/A 104
A6-02PV2X0700* N/A 6 N/A 7/.0612 N/A 0.169 N/A 0.085 N/A .69 N/A 50 N/A 134
A4-02PV2X0700* N/A 4 N/A 7/.0772 N/A 0.213 N/A 0.085 N/A .78 N/A 78 N/A 180
A2-02PV2X0700* N/A 2 N/A 7/.0974 N/A 0.268 N/A 0.085 N/A .89 N/A 126 N/A 244
A1-02PV2X1900* N/A 1 N/A 19/.0664 N/A 0.299 N/A 0.105 N/A 1.03 N/A 158 N/A 324
A1/0-02PV2X190* N/A 1/0 N/A 19/.0745 N/A 0.336 N/A 0.105 N/A 1.10 N/A 198 N/A 382
A2/0-02PV2X1900* N/A 2/0 N/A 19/.0837 N/A 0.376 N/A 0.105 N/A 1.08 N/A 250 N/A 450
A3/0-02PV2X1900* N/A 3/0 N/A 19/.0940 N/A 0.423 N/A 0.105 N/A 1.28 N/A 316 N/A 534
A4/0-02PV2X1900* N/A 4/0 N/A 19/.1055 N/A 0.475 N/A 0.105 N/A 1.38 N/A 398 N/A 638
A250-02PV2X3700* N/A 250 N/A 37/.0822 N/A 0.520 N/A 0.120 N/A 1.53 N/A 524 N/A 826
A300-02PV2X3700* N/A 300 N/A 37/.0900 N/A 0.570 N/A 0.120 N/A 1.63 N/A 564 N/A 890
A350-02PV2X3700* N/A 350 N/A 37/.0972 N/A 0.616 N/A 0.120 N/A 1.72 N/A 658 N/A 1006
A400-02PV2X3700* N/A 400 N/A 37/.1040 N/A 0.659 N/A 0.120 N/A 1.81 N/A 752 N/A 1122
A500-02PV2X3700* N/A 500 N/A 37/.1159 N/A 0.736 N/A 0.120 N/A 1.96 N/A 942 N/A 1350
A600-02PV2X6100* N/A 600 N/A 61/.0992 N/A 0.813 N/A 0.135 N/A 2.18 N/A 1130 N/A 1636
A750-02PV2X6100* N/A 750 N/A 61/.1109 N/A 0.908 N/A 0.135 N/A 2.37 N/A 1412 N/A 1970
A1000-02PV2X6100* N/A 1000 N/A 61/.1280 N/A 1.060 N/A 0.135 N/A 2.67 N/A 1828 N/A 2470