ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
All Categories > APPENDIX > Insulation Performance Specifications > TRXLPE Performance Specifications > View Items  

TRXLPE Performance Specifications

Check up to five results to perform an action.

Suitable for Use for the following specifications

  • AEIC CS8
  • ICEA S-94-649
  • ICEA T-31-610
  • ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable
  • UL 1072 MV-90 or MV-105
  • CSA Standard C68.5-07


ICEA T-34-664 as applicable for TRXLPE insulated concentric neutral cable must conform to the following chart:

PHYSICAL PROPERTIES

UNIT

TEST METHOD

VALUE

Density(Base Resin)

g/cm3

ASTM D1505

0.921

Tensile Strength

kg/ cm2

ASTM D638

200

Elongation

%

ASTM D638

550

Oven Aging @ 135 ℃, 7 days

 

 

 

Tensile Strength Retention

%

ASTM D638

> 90

Elongation Retention

%

ASTM D638

> 90

Hot/Set @ 200℃, 20N/cm2

 

IEC-60811-2-1

 

Hot Elongation

%

 

< 100

Permanent Set

%

 

< 5

Cure Behavior @ 180℃ (MDR)

 

HCY-I-24196

 

Ts1

minute

 

> 1

Tc90

minute

 

< 5

Mh-MI

lb・in

 

> 4.5

Moisture

ppm

HCY-I-24205

< 200

ELECTRICAL PROPERTIES

UNIT

TEST METHOD

VALUE

Dielectric Constant @ 1 MHz

-

ASTM D150

< 2.3

Dissipation Factor @ 1 MHz

-

ASTM D150

< 0.0005

Dielectric Strength

kV/mm

ASTM D149

> 20

DC Volume Resistivity

ohm cm

ASTM D257

> 1016

TREE RESISTANCE

UNIT

TEST METHOD

VALUE

Relative Bow-tie Tree Size

%

Internal

< 15

Resistance to Water Tree

 

 

 

Growth @25℃, 30days

%

Internal

< 0.1



1. Tree test conditions: Frequency=1kHz, Applied Voltage=5kV, 0.01M NaCl Solution.

2. Values are typical : not to be construed for specification.

 








    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  