ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 35 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV.
Notes
Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 10 of 10 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

345-EPR-06 N/A 1/0 N/A Solid N/A 6 N/A 14 N/A 0.325 Inches N/A 1.075 Inches N/A 1.195 Inches N/A 1.323 Inches N/A 1.423 Inches N/A 736 Lbs N/A 815 Lbs N/A 215 Amps N/A 165 Amps N/A 145 Amps
345-EPR-07 N/A 1/0 N/A 19 N/A 6 N/A 14 N/A 0.370 Inches N/A 1.120 Inches N/A 1.230 Inches N/A 1.350 Inches N/A 1.460 Inches N/A 835 Lbs N/A 935 Lbs N/A 215 Amps N/A 165 Amps N/A 145 Amps
345-EPR-08 N/A 2/0 N/A 19 N/A 7 N/A 14 N/A 0.420 Inches N/A 1.170 Inches N/A 1.270 Inches N/A 1.400 Inches N/A 1.500 Inches N/A 925 Lbs N/A 1044 Lbs N/A 245 Amps N/A 190 Amps N/A 167 Amps
345-EPR-09 N/A 3/0 N/A 19 N/A 9 N/A 14 N/A 0.470 Inches N/A 1.220 Inches N/A 1.320 Inches N/A 1.480 Inches N/A 1.590 Inches N/A 1018 Lbs N/A 1138 Lbs N/A 275 Amps N/A 215 Amps N/A 189 Amps
345-EPR-10 N/A 4/0 N/A 19 N/A 11 N/A 14 N/A 0.530 Inches N/A 1.280 Inches N/A 1.380 Inches N/A 1.540 Inches N/A 1.710 Inches N/A 1161 Lbs N/A 1286 Lbs N/A 305 Amps N/A 245 Amps N/A 215 Amps
345-EPR-11 N/A 250 N/A 37 N/A 13 N/A 14 N/A 0.570 Inches N/A 1.330 Inches N/A 1.440 Inches N/A 1.640 Inches N/A 1.810 Inches N/A 1301 Lbs N/A 1484 Lbs N/A 335 Amps N/A 270 Amps N/A 238 Amps
345-EPR-12 N/A 350 N/A 37 N/A 11 N/A 12 N/A 0.680 Inches N/A 1.440 Inches N/A 1.540 Inches N/A 1.700 Inches N/A 1.890 Inches N/A 1558 Lbs N/A 1752 Lbs N/A 390 Amps N/A 320 Amps N/A 280 Amps
345-EPR-13 N/A 500 N/A 37 N/A 16 N/A 12 N/A 0.810 Inches N/A 1.570 Inches N/A 1.720 Inches N/A 1.880 Inches N/A 2.040 Inches N/A 2003 Lbs N/A 2213 Lbs N/A 440 Amps N/A 385 Amps N/A 338 Amps
345-EPR-14 N/A 750 N/A 61 N/A 15 N/A 10 N/A 0.990 Inches N/A 1.760 Inches N/A 1.930 Inches N/A 2.110 Inches N/A 2.280 Inches N/A 2590 Lbs N/A 2850 Lbs N/A 515 Amps N/A 475 Amps N/A 417 Amps
345-EPR-15 N/A 1000 N/A 61 N/A 20 N/A 10 N/A 1.140 Inches N/A 1.920 Inches N/A 2.060 Inches N/A 2.270 Inches N/A 2.430 Inches N/A 3143 Lbs N/A 3415 Lbs N/A 570 Amps N/A 535 Amps N/A 470 Amps