Applications
For use on single phase and three phase primary underground distribution systems operating at 35 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV.
Notes
Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 9 of 9 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

345-EPR-20 N/A 1/0 N/A 19 N/A 9 N/A 14 N/A 0.370 Inches N/A 1.120 Inches N/A 1.230 Inches N/A 1.350 Inches N/A 1.460 Inches N/A 1102 Lbs N/A 1221 Lbs N/A 270 Amps N/A 215 Amps N/A 189 Amps
345-EPR-21 N/A 2/0 N/A 19 N/A 11 N/A 14 N/A 0.420 Inches N/A 1.170 Inches N/A 1.270 Inches N/A 1.400 Inches N/A 1.500 Inches N/A 1264 Lbs N/A 1384 Lbs N/A 305 Amps N/A 240 Amps N/A 211 Amps
345-EPR-22 N/A 3/0 N/A 19 N/A 14 N/A 14 N/A 0.470 Inches N/A 1.220 Inches N/A 1.320 Inches N/A 1.480 Inches N/A 1.590 Inches N/A 1444 Lbs N/A 1569 Lbs N/A 340 Amps N/A 280 Amps N/A 246 Amps
345-EPR-23 N/A 4/0 N/A 19 N/A 11 N/A 12 N/A 0.530 Inches N/A 1.280 Inches N/A 1.380 Inches N/A 1.540 Inches N/A 1.710 Inches N/A 1691 Lbs N/A 1874 Lbs N/A 380 Amps N/A 315 Amps N/A 276 Amps
345-EPR-24 N/A 250 N/A 37 N/A 13 N/A 12 N/A 0.570 Inches N/A 1.330 Inches N/A 1.440 Inches N/A 1.640 Inches N/A 1.810 Inches N/A 1939 Lbs N/A 2133 Lbs N/A 405 Amps N/A 340 Amps N/A 298 Amps
345-EPR-25 N/A 350 N/A 37 N/A 12 N/A 10 N/A 0.680 Inches N/A 1.440 Inches N/A 1.540 Inches N/A 1.700 Inches N/A 1.890 Inches N/A 2469 Lbs N/A 2679 Lbs N/A 460 Amps N/A 400 Amps N/A 350 Amps
345-EPR-26 N/A 500 N/A 37 N/A 17 N/A 10 N/A 0.810 Inches N/A 1.570 Inches N/A 1.720 Inches N/A 1.880 Inches N/A 2.040 Inches N/A 3273 Lbs N/A 3533 Lbs N/A 520 Amps N/A 470 Amps N/A 412 Amps
345-EPR-27 N/A 750 N/A 61 N/A 25 N/A 10 N/A 0.990 Inches N/A 1.760 Inches N/A 1.930 Inches N/A 2.110 Inches N/A 2.280 Inches N/A 4504 Lbs N/A 4776 Lbs N/A 567 Amps N/A 550 Amps N/A 483 Amps
345-EPR-28 N/A 1000 N/A 61 N/A 33 N/A 10 N/A 1.140 Inches N/A 1.920 Inches N/A 2.060 Inches N/A 2.270 Inches N/A 2.430 Inches N/A 5647 Lbs N/A 5647 Lbs N/A 625 Amps N/A 615 Amps N/A 540 Amps
1 - 9 of 9 | Results Per Page | View | Unit of Measure