A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 25 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000 V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 7 of 7 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
1/C
Direct
Buried

Ampacity
1/C
Duct
Buried

Ampacity
1/C
Duct In Air

260-EPR-01 N/A 1 N/A Solid N/A 13 N/A 14 N/A 0.289 Inches N/A 0.870 Inches N/A 0.950 Inches N/A 1.078 Inches N/A 1.178 Inches N/A 657 Lbs N/A 735 Lbs N/A 195 Amps N/A 145 Amps N/A 127 Amps
260-EPR-02 N/A 1 N/A 19 N/A 13 N/A 14 N/A 0.330 Inches N/A 0.910 Inches N/A 0.970 Inches N/A 1.100 Inches N/A 1.200 Inches N/A 676 Lbs N/A 757 Lbs N/A 195 Amps N/A 145 Amps N/A 127 Amps
260-EPR-03 N/A 1/0 N/A Solid N/A 16 N/A 14 N/A 0.325 Inches N/A 0.905 Inches N/A 0.989 Inches N/A 1.117 Inches N/A 1.217 Inches N/A 736 Lbs N/A 815 Lbs N/A 220 Amps N/A 165 Amps N/A 145 Amps
260-EPR-04 N/A 1/0 N/A 19 N/A 16 N/A 14 N/A 0.370 Inches N/A 0.950 Inches N/A 1.010 Inches N/A 1.140 Inches N/A 1.240 Inches N/A 762 Lbs N/A 845 Lbs N/A 220 Amps N/A 165 Amps N/A 145 Amps
260-EPR-05 N/A 2/0 N/A 19 N/A 13 N/A 12 N/A 0.420 Inches N/A 0.990 Inches N/A 1.060 Inches N/A 1.190 Inches N/A 1.290 Inches N/A 886 Lbs N/A 986 Lbs N/A 250 Amps N/A 190 Amps N/A 167 Amps
260-EPR-06 N/A 3/0 N/A 19 N/A 16 N/A 12 N/A 0.470 Inches N/A 1.040 Inches N/A 1.150 Inches N/A 1.310 Inches N/A 1.410 Inches N/A 1038 Lbs N/A 1141 Lbs N/A 290 Amps N/A 210 Amps N/A 185 Amps
260-EPR-07 N/A 4/0 N/A 19 N/A 20 N/A 12 N/A 0.530 Inches N/A 1.100 Inches N/A 1.210 Inches N/A 1.370 Inches N/A 1.470 Inches N/A 1233 Lbs N/A 1340 Lbs N/A 325 Amps N/A 245 Amps N/A 215 Amps