A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 25 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000 V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 9 of 9 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

260-EPR-23 N/A 1/0 N/A 19 N/A 9 N/A 14 N/A 0.370 Inches N/A 0.950 Inches N/A 1.010 Inches N/A 1.140 Inches N/A 1.240 Inches N/A 896 Lbs N/A 996 Lbs N/A 275 Amps N/A 215 Amps N/A 189 Amps
260-EPR-24 N/A 2/0 N/A 19 N/A 11 N/A 14 N/A 0.420 Inches N/A 0.990 Inches N/A 1.060 Inches N/A 1.190 Inches N/A 1.290 Inches N/A 1045 Lbs N/A 1148 Lbs N/A 310 Amps N/A 250 Amps N/A 220 Amps
260-EPR-25 N/A 3/0 N/A 19 N/A 14 N/A 14 N/A 0.470 Inches N/A 1.040 Inches N/A 1.150 Inches N/A 1.310 Inches N/A 1.410 Inches N/A 1246 Lbs N/A 1353 Lbs N/A 345 Amps N/A 285 Amps N/A 250 Amps
260-EPR-26 N/A 4/0 N/A 19 N/A 11 N/A 12 N/A 0.530 Inches N/A 1.100 Inches N/A 1.210 Inches N/A 1.390 Inches N/A 1.490 Inches N/A 1491 Lbs N/A 1634 Lbs N/A 385 Amps N/A 320 Amps N/A 280 Amps
260-EPR-27 N/A 250 N/A 37 N/A 13 N/A 12 N/A 0.570 Inches N/A 1.160 Inches N/A 1.260 Inches N/A 1.490 Inches N/A 1.590 Inches N/A 1724 Lbs N/A 1896 Lbs N/A 410 Amps N/A 345 Amps N/A 303 Amps
260-EPR-28 N/A 350 N/A 37 N/A 12 N/A 10 N/A 0.680 Inches N/A 1.260 Inches N/A 1.400 Inches N/A 1.570 Inches N/A 1.740 Inches N/A 2239 Lbs N/A 2423 Lbs N/A 460 Amps N/A 405 Amps N/A 355 Amps
260-EPR-29 N/A 500 N/A 37 N/A 17 N/A 10 N/A 0.810 Inches N/A 1.400 Inches N/A 1.500 Inches N/A 1.700 Inches N/A 1.870 Inches N/A 2951 Lbs N/A 3185 Lbs N/A 520 Amps N/A 470 Amps N/A 412 Amps
260-EPR-30 N/A 750 N/A 61 N/A 25 N/A 10 N/A 0.990 Inches N/A 1.590 Inches N/A 1.730 Inches N/A 1.940 Inches N/A 2.100 Inches N/A 4208 Lbs N/A 4453 Lbs N/A 567 Amps N/A 550 Amps N/A 483 Amps
260-EPR-31 N/A 1000 N/A 61 N/A 33 N/A 10 N/A 1.140 Inches N/A 1.740 Inches N/A 1.890 Inches N/A 2.090 Inches N/A 2.260 Inches N/A 5331 Lbs N/A 5331 Lbs N/A 625 Amps N/A 615 Amps N/A 540 Amps