A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 15 kV phase to phase at 100 % and 133 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000 V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 10 of 10 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

220-EPR-10 N/A 1/0 N/A Solid N/A 6 N/A 14 N/A 0.325 Inches N/A 0.825 Inches N/A 0.905 Inches N/A 1.033 Inches N/A 1.133 Inches N/A 541 Lbs N/A 616 Lbs N/A 230 Amps N/A 165 Amps N/A 145 Amps
220-EPR-11 N/A 1/0 N/A 19 N/A 6 N/A 14 N/A 0.370 Inches N/A 0.870 Inches N/A 0.930 Inches N/A 1.060 Inches N/A 1.161 Inches N/A 558 Lbs N/A 631 Lbs N/A 230 Amps N/A 165 Amps N/A 145 Amps
220-EPR-12 N/A 2/0 N/A 19 N/A 7 N/A 14 N/A 0.420 Inches N/A 0.910 Inches N/A 0.980 Inches N/A 1.100 Inches N/A 1.207 Inches N/A 628 Lbs N/A 715 Lbs N/A 250 Amps N/A 190 Amps N/A 167 Amps
220-EPR-13 N/A 3/0 N/A 19 N/A 9 N/A 14 N/A 0.470 Inches N/A 0.960 Inches N/A 1.030 Inches N/A 1.190 Inches N/A 1.291 Inches N/A 708 Lbs N/A 797 Lbs N/A 280 Amps N/A 215 Amps N/A 189 Amps
220-EPR-14 N/A 4/0 N/A 19 N/A 11 N/A 14 N/A 0.530 Inches N/A 1.020 Inches N/A 1.120 Inches N/A 1.270 Inches N/A 1.369 Inches N/A 863 Lbs N/A 956 Lbs N/A 320 Amps N/A 245 Amps N/A 215 Amps
220-EPR-15 N/A 250 N/A 37 N/A 13 N/A 14 N/A 0.570 Inches N/A 1.080 Inches N/A 1.180 Inches N/A 1.370 Inches N/A 1.469 Inches N/A 978 Lbs N/A 1092 Lbs N/A 345 Amps N/A 270 Amps N/A 237 Amps
220-EPR-16 N/A 350 N/A 37 N/A 11 N/A 12 N/A 0.680 Inches N/A 1.180 Inches N/A 1.290 Inches N/A 1.450 Inches N/A 1.552 Inches N/A 1219 Lbs N/A 1369 Lbs N/A 405 Amps N/A 325 Amps N/A 285 Amps
220-EPR-17 N/A 500 N/A 37 N/A 16 N/A 12 N/A 0.810 Inches N/A 1.310 Inches N/A 1.420 Inches N/A 1.580 Inches N/A 1.746 Inches N/A 1555 Lbs N/A 1715 Lbs N/A 460 Amps N/A 385 Amps N/A 338 Amps
220-EPR-18 N/A 750 N/A 61 N/A 15 N/A 10 N/A 0.990 Inches N/A 1.510 Inches N/A 1.610 Inches N/A 1.810 Inches N/A 1.980 Inches N/A 2144 Lbs N/A 2349 Lbs N/A 515 Amps N/A 475 Amps N/A 417 Amps
220-EPR-19 N/A 1000 N/A 61 N/A 20 N/A 10 N/A 1.140 Inches N/A 1.660 Inches N/A 1.810 Inches N/A 2.010 Inches N/A 2.175 Inches N/A 2667 Lbs N/A 2882 Lbs N/A 565 Amps N/A 540 Amps N/A 475 Amps