ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 9 of 9 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

175-EPR-26 N/A 1/0 N/A 19 N/A 9 N/A 14 N/A 0.370 Inches N/A 0.770 Inches N/A 0.840 Inches N/A 0.970 Inches N/A 1.070 Inches N/A 749 Lbs N/A 814 Lbs N/A 290 Amps N/A 210 Amps N/A 185 Amps
175-EPR-27 N/A 2/0 N/A 19 N/A 11 N/A 14 N/A 0.420 Inches N/A 0.820 Inches N/A 0.880 Inches N/A 1.010 Inches N/A 1.110 Inches N/A 891 Lbs N/A 969 Lbs N/A 320 Amps N/A 240 Amps N/A 210 Amps
175-EPR-28 N/A 3/0 N/A 19 N/A 14 N/A 14 N/A 0.470 Inches N/A 0.870 Inches N/A 0.930 Inches N/A 1.100 Inches N/A 1.200 Inches N/A 1056 Lbs N/A 1135 Lbs N/A 350 Amps N/A 275 Amps N/A 241 Amps
175-EPR-29 N/A 4/0 N/A 19 N/A 11 N/A 12 N/A 0.530 Inches N/A 0.930 Inches N/A 0.990 Inches N/A 1.150 Inches N/A 1.250 Inches N/A 1267 Lbs N/A 1348 Lbs N/A 390 Amps N/A 315 Amps N/A 276 Amps
175-EPR-30 N/A 250 N/A 37 N/A 13 N/A 12 N/A 0.570 Inches N/A 0.990 Inches N/A 1.050 Inches N/A 1.190 Inches N/A 1.290 Inches N/A 1487 Lbs N/A 1597 Lbs N/A 415 Amps N/A 340 Amps N/A 298 Amps
175-EPR-31 N/A 350 N/A 37 N/A 12 N/A 10 N/A 0.680 Inches N/A 1.090 Inches N/A 1.190 Inches N/A 1.360 Inches N/A 1.460 Inches N/A 2022 Lbs N/A 2164 Lbs N/A 475 Amps N/A 415 Amps N/A 364 Amps
175-EPR-32 N/A 500 N/A 37 N/A 17 N/A 10 N/A 0.810 Inches N/A 1.220 Inches N/A 1.330 Inches N/A 1.490 Inches N/A 1.590 Inches N/A 2712 Lbs N/A 2860 Lbs N/A 525 Amps N/A 480 Amps N/A 420 Amps
175-EPR-33 N/A 750 N/A 61 N/A 25 N/A 10 N/A 0.990 Inches N/A 1.410 Inches N/A 1.520 Inches N/A 1.720 Inches N/A 1.890 Inches N/A 3873 Lbs N/A 4063 Lbs N/A 560 Amps N/A 530 Amps N/A 465 Amps
175-EPR-34 N/A 1000 N/A 61 N/A 33 N/A 10 N/A 1.140 Inches N/A 1.570 Inches N/A 1.710 Inches N/A 1.920 Inches N/A 2.030 Inches N/A 5028 Lbs N/A 5231 Lbs N/A 600 Amps N/A 590 Amps N/A 518 Amps