A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% insulation level. Suitable for either direct burial or installation in ducts.

Construction
Aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5,000 - 46,000V
  • ICEA T-31-610 Guide for Conducting a Longitudinal Water Penetration Resistance Tests on Blocked Conductors
  • ICEA T-34-664 Test Method for Conducting Longitudinal Water Penetration Resistance Tests on Longitudinal Water Blocked Cables
Notes
  • Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit.
1 - 10 of 10 | Results Per Page | View | Unit of Measure
1 

Item #

Conductor
Size AWG

Conductor
Stranding

Copper
Neutral
No. of
Wires

Copper
Neutral
Size
AWG

Conductor
Diameter

Diameter
Over
Insulation

Diameter
Over
Insulation
Shield

Diameter
Over
Neutral
Wires

Diameter
Over
Embedded
Jacket

Total w/o Jacket Weight

Total w/ Embedded Jacket Weight

Ampacity
3/C
Direct Buried

Ampacity
3/C
Triplex Buried

Ampacity
3/C
Duct In Air

175-EPR-10 N/A 1/0 N/A Solid N/A 6 N/A 14 N/A 0.325 Inches N/A 0.735 Inches N/A 0.815 Inches N/A 0.943 Inches N/A 1.043 Inches N/A 471 Lbs N/A 539 Lbs N/A 230 Amps N/A 165 Amps N/A 145 Amps
175-EPR-11 N/A 1/0 N/A 19 N/A 6 N/A 14 N/A 0.370 Inches N/A 0.770 Inches N/A 0.840 Inches N/A 0.970 Inches N/A 1.070 Inches N/A 482 Lbs N/A 547 Lbs N/A 230 Amps N/A 165 Amps N/A 145 Amps
175-EPR-12 N/A 2/0 N/A 19 N/A 7 N/A 14 N/A 0.420 Inches N/A 0.820 Inches N/A 0.880 Inches N/A 0.010 Inches N/A 1.110 Inches N/A 552 Lbs N/A 630 Lbs N/A 250 Amps N/A 190 Amps N/A 167 Amps
175-EPR-13 N/A 3/0 N/A 19 N/A 9 N/A 14 N/A 0.470 Inches N/A 0.870 Inches N/A 0.930 Inches N/A 0.100 Inches N/A 1.200 Inches N/A 630 Lbs N/A 709 Lbs N/A 280 Amps N/A 215 Amps N/A 189 Amps
175-EPR-14 N/A 4/0 N/A 19 N/A 11 N/A 14 N/A 0.530 Inches N/A 0.930 Inches N/A 0.990 Inches N/A 0.130 Inches N/A 1.230 Inches N/A 737 Lbs N/A 818 Lbs N/A 320 Amps N/A 245 Amps N/A 215 Amps
175-EPR-15 N/A 250 N/A 37 N/A 13 N/A 14 N/A 0.570 Inches N/A 0.990 Inches N/A 1.050 Inches N/A 0.170 Inches N/A 1.270 Inches N/A 849 Lbs N/A 959 Lbs N/A 345 Amps N/A 270 Amps N/A 237 Amps
175-EPR-16 N/A 350 N/A 37 N/A 11 N/A 12 N/A 0.680 Inches N/A 1.090 Inches N/A 1.190 Inches N/A 0.360 Inches N/A 1.460 Inches N/A 1111 Lbs N/A 1253 Lbs N/A 405 Amps N/A 325 Amps N/A 285 Amps
175-EPR-17 N/A 500 N/A 37 N/A 16 N/A 12 N/A 0.810 Inches N/A 1.220 Inches N/A 1.330 Inches N/A 1.490 Inches N/A 1.590 Inches N/A 1442 Lbs N/A 1590 Lbs N/A 460 Amps N/A 385 Amps N/A 338 Amps
175-EPR-18 N/A 750 N/A 61 N/A 15 N/A 10 N/A 0.990 Inches N/A 1.410 Inches N/A 1.520 Inches N/A 1.720 Inches N/A 1.890 Inches N/A 1959 Lbs N/A 2149 Lbs N/A 515 Amps N/A 475 Amps N/A 417 Amps
175-EPR-19 N/A 1000 N/A 61 N/A 20 N/A 10 N/A 1.140 Inches N/A 1.570 Inches N/A 1.710 Inches N/A 1.920 Inches N/A 2.030 Inches N/A 2524 Lbs N/A 2727 Lbs N/A 565 Amps N/A 540 Amps N/A 475 Amps
1 - 10 of 10 | Results Per Page | View | Unit of Measure