All Categories > Multiplex Cables (Overhead and Underground) > Copper Service Drop Cable 600V > Duplex Service Drop Cable
Copper Conductor
> Copper Duplex Service Drop Cable > View Items
 

Copper Duplex Service Drop Cable

Check up to five results to perform an action.

Application
Used to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. Also suitable for installations for street lighting, security lights, and temporary service for construction. To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 ºC for polyethylene insulated conductors and 90 ºC for cross-linked polyethylene (XLP) insulated conductors.

Specifications
Meets or exceeds the following ASTM specifications:
  • B-1 Hard-Drawn Copper Wire.
  • B-3 Soft or Annealed Copper Wire.
  • B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft.
Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474 for polyethylene and cross-linked polyethylene insulated conductors.

Construction
Conductors are concentrically stranded compressed soft copper insulated with either cross-linked polyethylene, or conventional polyethylene.
Neutral messengers are either solid or concentrically stranded bare hard-drawn copper.

Notes:
  • Code words for XLP insulated products are formed by adding ""XLP"" to the conventional polyethylene code words above (e.g.-Theta/XLP).
  • Ampacity figures for black insulation only. Based on conductor temperature of 75 ºC for polyethylene insulated conductors, 90 ºC for XLP insulated conductors, ambient temperature of 40 ºC 2 ft./sec. wind in sun.
"





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 7 of 7 1 

Item #

Phase
Conductor
Size
AWG

Phase
Conductor
Stranding

Phase
Conductor
Cover
Thickness
(mils)

Neutral
Messenger
Size
AWG

Neutral
Messenger
Stranding

Neutral
Messenger
Rated
Strength
(lbs.)

Nominal
Lay
Length
(inches)

Weight
per MFT
XLP

Weight
per MFT
Poly

Allowable
Ampacities
XLP

Allowable
Ampacities
Poly

Theta 8 7 45 10 1 529 10.36 96 97 85 70
Omega 8 1 45 8 1 826 10.36 112 113 85 70
Iota 8 7 45 8 1 826 10.36 115 116 85 70
Kappa 8 7 45 8 7 777 10.36 116 117 85 70
Lambda 6 7 45 8 1 826 10.36 149 149 110 90
Omicron 6 7 45 6 1 1280 10.36 179 179 110 90
Sigma 6 7 45 6 7 1228 10.36 180 181 110 90