Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 8000 (8176-H24) aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Black neutrals may be specified if desired.

Standards
Secondary URD duplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-800 8000 Series Aluminum Alloy Wire for Electrical Purposes
  • B-801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy for Subsequent Covering or Insulation.
  • B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
  • Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • UL Standard 44 for Type RHH or RHW-2
  • UL standard 854 for Type USE-2.
Options
  • Cable in Duct
  • Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 90, 100% load factor. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
1 - 4 of 4 | Results Per Page | View | Unit of Measure
1 

Item #

Phase
Conductor
Size/AWG

Phase
Conductor
Stranding

Phase
Conductor
Insulation
Thickness

Neutral Size AWG

Neutral Stranding

Neutral Insulation Thickness

Single
Phase
Conductor

Outside
Diameter

Weight
(lb/1000 ft)

Ampacity
Direct Burial

Ampacity
In Duct

Sort by
N/A 8 N/A 7/w N/A 60 mls N/A 8 N/A 7/w N/A 60 mls N/A .262 Inches N/A .524 Inches N/A 76 Lbs N/A 70 Amps N/A 70 Amps
N/A 6 N/A 7/w N/A 60 mls N/A 6 N/A 7/w N/A 60 mls N/A .299 Inches N/A .596 Inches N/A 91 Lbs N/A 95 Amps N/A 70 Amps
N/A 4 N/A 7/w N/A 60 mls N/A 4 N/A 7/w N/A 60 mls N/A .345 Inches N/A .690 Inches N/A 129 Lbs N/A 125 Amps N/A 90 Amps
N/A 2 N/A 7/w N/A 60 mls N/A 2 N/A 7/w N/A 60 mls N/A .403 Inches N/A .806 Inches N/A 189 Lbs N/A 187 Amps N/A 100 Amps