USE-2 / RHH / RHW-2 EPR/CPE Copper Conductor 600V, 90°C Wet or Dry

Check up to five results to perform an action.

Applications
Recommended for use in all low voltage circuits where continuity of service is the prime consideration. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, directly buried in the earth, or lashed to a messenger for aerial installation. These cables may also be installed in cable tray (size 1/0 AWG and larger per NEC 392.2).  For use in free air, raceways or direct burial in accordance with NEC. 

Specifications
Conductor: Uncoated copper solid per ASTM-B-3, compress stranded per ASTM B-8, or compact per ASTM B-496. Insulation: Meets or exceeds all requirements of ICEA S-95-658/NEMA WC-70 and UL Standards 44 and 854. Jacket: CPE. Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2 or USE-2, VW-1. Sizes 1/0 AWG and larger are also marked "sunlight resistant, for use in cable tray." Listed by CSA as RW-90, -25C, FT1 (1/0 and larger FT4), outdoor.

Product Features
  • Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
  • Passes the IEEE 383-1974 Vertical Tray Flame Test.
  • Passes the IEEE 1202-1991 Vertical Tray Flame Test. (sizes 1/0 AWG & larger).
  • Extreme heat resistance; 90 ºC continuous rating, wet or dry 110 ºC hot spot rating 130 ºC emergency overload rating 250 ºC short circuit rating
Notes
These ampacities are based on single conductor in free air, 40 ºC ambient air temperature, 90 ºC conductor operating temperature.

Options
PVC or LSOH jacket





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 15 of 15 1 

Item #

Conductor
Size
AWG
MCM
(lb)

Conductor
Stranding

Conductor
Diameter
(in)

Nominal
Insulation
(in)

Nominal
Jacket
Thickness
Min.
(in)

Nominal
Jacket
Thickness
Min.
(mm)

Nominal
Jacket
Thickness
Approximate
(in)

Nominal
Jacket
Thickness
Approximate
(mm)

Nominal
Jacket
Thickness
Max.
(in)

Nominal
Jacket
Thickness
Max.
(mm)

Nominal
O.D.
(in)

Approximate
Weight
/MFT

Ampacity
40 ºC
Ambient
Temp.

USE2-14 14 AWG 7 0.072 0.03 0.161 4.1 0.165 4.2 0.177 4.5 0.236 24 25
USE2-12 12 AWG 7 0.091 0.03 0.185 4.7 0.189 4.8 0.205 5.2 0.256 34 32
USE2-10 10 AWG 7 0.116 0.03 0.205 5.2 0.213 5.4 0.228 5.8 0.29 49 47
USE2-8 8 AWG 7 0.146 0.045 0.268 6.8 0.276 7 0.299 7.6 0.333 79 83
USE2-6 6 AWG 7 0.183 0.045 0.335 8.5 0.346 8.8 0.374 9.5 0.403 124 109
USE2-4 4 AWG 7 0.231 0.045 0.382 9.7 0.394 10 0.425 10.8 0.461 179 145
USE2-2 2 AWG 7 0.292 0.045 0.441 11.2 0.453 11.5 0.488 12.4 0.51 260 192
USE2-1/0 1/0 AWG 19 0.373 0.055 0.559 14.2 0.575 14.6 0.622 15.8 0.7 420 258
USE2-2/0 2/0 AWG 19 0.419 0.055 0.602 15.3 0.619 15.73 0.669 17 0.74 513 298
USE2-4/0 4/0 AWG 19 0.528 0.055 0.717 18.2 0.736 18.7 0.795 20.2 0.87 774 400
USE2-250 250 MCM 37 0.575 0.065 0.827 21 0.85 21.6 0.917 23.3 0.99 956 445
USE2-350 350 MCM 37 0.681 0.065 0.929 23.6 0.957 24.3 1.031 26.2 1.055 1290 552
USE2-500 500 MCM 37 0.813 0.065 1.055 26.8 1.088 27.64 1.177 29.9 1.125 1798 695
USE2-750 750 MCM 61 0.98 0.08 1.264 32.1 1.303 33.1 1.406 35.7 1.205 2686 898
USE2-1000 1000 MCM 61 1.152 0.08 1.413 35.9 1.457 37 1.575 40 1.305 3463 1076