Applications
Control or signal cable for important circuits in industrial plants and station control cable for electric utilities where flame resistance is essential. Suitable for the operation and interconnection of protective devices; rated circuit voltage 600 volts; recommended for operation at 90 ºC maximum continuous conductor temperature in wet or dry locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, and are suitable for direct burial. Utility grade meets or exceeds all UL requirements.

Construction
Stranded coated copper conductors. The insulation shall be either fire retardant ethylene propylene rubber (EPR) or fire retardant cross-linked Polyethylene (FR-XLPE). ICEA Appendix E Method 1 color-coded, conductors twisted with suitable fillers, helically applied copper tape shield, CPE jacket overall, surface printed.

Standards
  • TC Type Tray Cable per Article 340 of the NEC.
  • Individual conductors pass UL Standard 44 and the VW-1 vertical flame test.
  • Individual conductors approved as Type XHHW.
  • Cables Pass IEEE-383 ribbon burner flame test.
  • Overall jacket approved as Sunlight Resistant.
  • Cables meet requirements of ICEA Pub. No. S-73-532/NEMA WC74
Notes
  • Cables may be supplied with an insulated ground and marked ""Open Wiring.""
  • Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73-532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
Options
  • Bare or Tinned Copper
  • Flexible stranded conductors
  • Color coding: ICEA Method 1, Table E1
  • EPR Insulation
  • PVC, CSPE, LSOH jackets
  • Insulated ground wires or bare ground wires
  • Overall copper tape shield
  • Overall copper braid shield
  • Overall longitudinal corrugated copper shield
  • Overall mylar tape shield with drain wire
  • 1000 volt rated construction
Consult AWG for a variety of alternate constructions for specific applications.
1 - 20 of 20 | Results Per Page | View | Unit of Measure
1 

Item #

Number
of
Conductors

Conductor
Size AWG

Number
of
Strands

Overall Mils

Overall
Diameter
Inches
(mm)

Weight
Per
(lb/1000 ft)
XLP

Sort by
N/A 2 N/A 10 N/A 7 N/A 45 N/A 0.52 N/A 190 Lbs
N/A 3 N/A 10 N/A 7 N/A 60 N/A 0.62 N/A 255 Lbs
N/A 4 N/A 10 N/A 7 N/A 60 N/A 0.68 N/A 320 Lbs
N/A 5 N/A 10 N/A 7 N/A 60 N/A 0.73 N/A 370 Lbs
N/A 6 N/A 10 N/A 7 N/A 60 N/A 0.80 N/A 440 Lbs
N/A 7 N/A 10 N/A 7 N/A 60 N/A 0.85 N/A 450 Lbs
N/A 8 N/A 10 N/A 7 N/A 80 N/A 1.05 N/A 755 Lbs
N/A 12 N/A 10 N/A 7 N/A 80 N/A 1.10 N/A 810 Lbs
N/A 14 N/A 10 N/A 7 N/A 80 N/A 1.14 N/A 920 Lbs
N/A 15 N/A 10 N/A 7 N/A 80 N/A 1.20 N/A 995 Lbs
N/A 16 N/A 10 N/A 7 N/A 80 N/A 1.24 N/A 1020 Lbs
N/A 18 N/A 10 N/A 7 N/A 80 N/A 1.27 N/A 1140 Lbs
N/A 19 N/A 10 N/A 7 N/A 80 N/A 1.27 N/A 1155 Lbs
N/A 20 N/A 10 N/A 7 N/A 80 N/A 1.34 N/A 1255 Lbs
N/A 25 N/A 10 N/A 7 N/A 80 N/A 1.48 N/A 1600 Lbs
N/A 27 N/A 10 N/A 7 N/A 80 N/A 1.52 N/A 1625 Lbs
N/A 29 N/A 10 N/A 7 N/A 80 N/A 1.54 N/A 1730 Lbs
N/A 31 N/A 10 N/A 7 N/A 80 N/A 1.60 N/A 1950 Lbs
N/A 32 N/A 10 N/A 7 N/A 80 N/A 1.63 N/A 1950 Lbs
N/A 37 N/A 10 N/A 7 N/A 80 N/A 1.70 N/A 2120 Lbs
1 - 20 of 20 | Results Per Page | View | Unit of Measure