> Control Cable
EPR Insulated Conductors, PVC Jacket, 600V
> 14 AWG EPR, PVC Jacket, 600V > View Items
 

14 AWG EPR, PVC Jacket, 600V

Check up to five results to perform an action.

Applications
As flame-retardant multi-conductor control, signal or power cables rated 600 volts, 90 ºC in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.

Construction
Stranded uncoated copper conductors, 30 mils Flame Retardant Ethylene Propylene Rubber (FR-EPR) insulation, color coded, two conductors flat, three or more conductors twisted with suitable fillers where necessary to make round, cable tape, PVC jacket overall, surface printed.

Standards
  • Listed by UL as Type TC per Standard 1277 for Tray Cables.
  • Cables UL listed for Direct Burial.
  • Individual conductors pass UL VW-1 flame test.
  • Individual conductors UL listed as Type XHHW-2.
  • Overall jacket UL listed as Sunlight Resistant.
  • Cables with grounding conductor UL listed for Open Wiring.
  • Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hour test.
  • Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
  • Cables meet requirements of ICEA S-73-532, NEMA WC70 for Control Cables.
Notes
  • Cables may be supplied with an insulated ground and marked ""Open Wiring.""
  • Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73-532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.
  • Color Coding also available ICEA Method 1, Table E-1; power sizes, ICEA Method 4.
Options
  • Bare or Tinned Copper
  • Flexible stranded conductors
  • E1 or E2 color codes
  • EPR Insulation
  • CPE, CSPE, LSOH jackets
  • Overall copper tape shield
  • Overall copper braid shield
  • Overall longitudinal corrugated copper shield
  • Overall Mylar tape shield with drain wire
  • 1000 volt rated construction
Consult AWG for a variety of alternate constructions for specific applications.





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 11 of 11 1 

Item #

No. of
Conductors

Size
AWG

Number
of
Strands

Nominal
Insulation
Thickness
(in)

Nominal
Insulation
Thickness
(mm)

Nominal
Jacket
Thickness
(in)

Nominal
Jacket
Thickness
(mm)

Nominal
Cable
O.D.
(in)

Nominal
Cable
O.D.
(mm)

Copper
Weight
lbs/MFT

Copper
Weight
kg/km

Approximate
Cable
Weight
/MFT
(lb)

Approximate
Cable
Weight
/MFT
(kg)

14-E-PVC-2-FLAT 2 FLAT 14 7/.0242 0.030 0.76 0.045 1.14 .365x.230 9.30x5.80 26 38 61 91
14-E-PVC-3 3 14 7/.0242 0.030 0.76 0.045 1.14 0.390 9.910 39 59 92 137
14-E-PVC-4 4 14 7/.0242 0.030 0.76 0.045 1.14 0.425 10.800 53 78 115 171
14-E-PVC-5 5 14 7/.0242 0.030 0.76 0.045 1.14 0.465 11.810 66 98 139 207
14-E-PVC-7 7 14 7/.0242 0.030 0.76 0.045 1.14 0.505 12.830 92 137 173 257
14-E-PVC-9 9 14 7/.0242 0.030 0.76 0.06 1.52 0.620 15.750 118 176 240 357
14-E-PVC-12 12 14 7/.0242 0.030 0.76 0.06 1.52 0.700 17.780 158 235 301 448
14-E-PVC-19 19 14 7/.0242 0.030 0.76 0.06 1.52 0.815 20.700 250 372 468 696
14-E-PVC-25 25 14 7/.0242 0.030 0.76 0.08 2.03 0.935 23.750 323 481 624 929
14-E-PVC-30 30 14 7/.0242 0.030 0.76 0.08 2.03 1.030 26.160 387 576 747 1112
14-E-PVC-37 37 14 7/.0242 0.030 0.76 0.08 2.03 1.110 28.190 466 694 875 1302