Applications
Used for overhead electrical distribution lines, ground ing electrical substations, electrical test equipment and any other electrical system. Suitable for numerous other applications.

Specifications
ASTM Specifications, latest issue, as follows :

Solid :
  • ASTM B-1 Hard Drawn Temper
  • ASTM B-2 Medium Hard Drawn Temper
  • ASTM B-3 Soft Drawn Temper
Notes
Ampacities (Amps per Cond.) are based on a 30 ºC ambient temperature, single conductor in air, per NEC.
1 - 7 of 7 | Results Per Page | View | Unit of Measure
1 

Item #

Size AWG
or
KCMIL

Number
of
Strands

Overall
Diameter

Weight
Per
MFT

Breaking
Strength
Soft

Breaking
Strength
Medium

Breaking
Strength
Hard

Allowable
Ampacity

SCC-01 N/A 14 N/A Solid N/A 0.064 Inches N/A 12.43 Lbs N/A 124.2 Lbs N/A 166.6 Lbs N/A 213.5 Lbs N/A 32 Amps
SCC-02 N/A 12 N/A Solid N/A 0.081 Inches N/A 19.77 Lbs N/A 197.5 Lbs N/A 261.2 Lbs N/A 336.9 Lbs N/A 41 Amps
SCC-03 N/A 10 N/A Solid N/A 0.102 Inches N/A 31.43 Lbs N/A 314 Lbs N/A 410.4 Lbs N/A 529.2 Lbs N/A 68 Amps
SCC-04 N/A 8 N/A Solid N/A 0.129 Inches N/A 49.98 Lbs N/A 479.8 Lbs N/A 643.9 Lbs N/A 826 Lbs N/A 95 Amps
SCC-05 N/A 6 N/A Solid N/A 0.162 Inches N/A 79.46 Lbs N/A 762.9 Lbs N/A 1010 Lbs N/A 1280 Lbs N/A 125 Amps
SCC-06 N/A 4 N/A Solid N/A 0.204 Inches N/A 126.4 Lbs N/A 1213 Lbs N/A 1584 Lbs N/A 1970 Lbs N/A 170 Amps
SCC-07 N/A 2 N/A Solid N/A 0.258 Inches N/A 200.9 Lbs N/A 1929 Lbs N/A 2450 Lbs N/A 3003 Lbs N/A 225 Amps
1 - 7 of 7 | Results Per Page | View | Unit of Measure