Application
These cables are suitable for use installed in cable trays, direct burial, and raceways, or when supported by a messenger wire. Voltage ratings not to exceeding 600 volts and conductor temperatures not to exceed 90°C dry or 90°C wet. Cables pass the UL 1277 Vertical Tray Flame Test and the IEEE 1202/FT4 flame test.

Construction
Conductor: Stranded Bare Annealed Copper made in Accordance with ASTM B-3, B-8, and B-174
Primary Insulation: The conductors are UL Type XHHW-2 per UL 44

#16 AWG Copper Control Wire: The insulation shall be colored as follows: 1 Black, 1 Red, 1Yellow, 1 Yellow/Black, 1 Blue, 1 White
#3 AWG Generator Wires: 1 Black, 1 Red, 1 White
#6 Ground Wire: 1
Cable Assembly: The insulated conductors are cabled together with fillers as necessary, and overall binder tape
Overall Jacket: A flame resistant and sunlight resistant PVC jacket is applied to the overall construction, 3 orange stripes
Cable Identification: Type: Surface print on jacket

Specifications
Type: Power Composite Installation Cable - TC-ER (Exposed Run)

  • 600 Volts, 90°C dry, 90° wet
  • XHHW-2 Conductors (XLPE)
  • PVC Jacket
  • UL Listed 1277 Type TC-ER
  • FT4 / IEEE 1202, Sunlight Resistant, Direct Burial
  • Joist Pull in accordance to UL 854

This specification covers the construction requirements of multi-conductor power cables in accordance with UL, Inc. Standard 1277, (UL) Listed as Type TC-ER. (Exposed Run). The construction consists of stranded, bare copper conductors with cross-lined polyethylene (XLPE) insulation. The conductors are cabled together and have a sunlight resistant, Polyvinyl Chloride (PVC) jacket.

No.

Item

Metric Unit

Inch - LB

1

Power phase 

1.1

number of cores

3

3

1.2

conductor 

 

1.2.1

material

Stranded Bare Annealed Copper made in Accordance with ASTM B-3, B-8

1.2.2

Cross section

26.7 mm2

3 AWG

1.2.3

number of wires

19

19

1.2.4

Diameter of wire

1.34

52.8 mils

1.2.5

Diameter of conductor

6.7

263.8 mils

1.3

Insulation

 

1.3.1

material

XLPE

1.3.2

Color code

1 Black, 1 Red, 1 White

1.3.2

Thickness of insulation

1.33 mm

52 mils

1.3.3

Min thickness

1.20 mm

47 mils

1.3.4

Diameter over insulation

9.36 mm

369 mils

1.3.5

Min diameter

9.23

363 mils

1.3.6

Max diameter

9.72

383 mils

2

Ground conductor

2.1

number of cores

1

1

2.2

conductor

 

2.2.1

material

Stranded Bare Annealed Copper made in Accordance with ASTM B-3, B-8

2.2.2

Cross section

13.3 mm2

6 AWG

2.2.3

number of wires

19

19

2.2.4

Diameter of wire

0.94

37 mils

2.2.5

Diameter of conductor

4.7

185 mils

2.3

Insulation

 

2.3.1

material

XLPE

2.3.2

Color code

1 Green

2.3.2

Thickness of insulation

0.94 mm

37 mils

2.3.3

Min thickness

0.85 mm

33 mils

2.3.4

Diameter over insulation

6.58 mm

259 mils

2.3.5

Min diameter

6.49

255 mils

2.3.6

Max diameter

6.83

269 mils

3

Control conductor

3.1

number of cores

 6

6

3.2

conductor

 

3.2.1

material

Stranded Bare Annealed Copper made in Accordance with ASTM B-3, B-8

3.2.2

Cross section

1.318 mm2

16 AWG

3.2.3

number of wires

16

16

3.2.4

Diameter of wire

0.324

12.8 mils

3.2.5

Diameter of conductor

1.49

58.7 mils

3.3

insulation

 

3.3.1

material

XLPE

3.3.2

Color code

1 Black, 1 Red, 1 Yellow, 1 Yellow/Black, 1 Blue, 1 White

3.3.2

Thickness of insulation

0.53 mm

21 mils

3.3.3

Min thickness

0.48 mm

19 mils

3.3.4

Diameter over insulation

2.55 mm

2100 mils

3.3.5

Min diameter

2.50

98 mils

3.3.6

Max diameter

2.69

106 mils

4

Cabling

4.1

6 control conductor in 2 groups

4.1.1

lay direction

Right

 

4.1.2

Filler

 

 

4.1.3

Lay length

40-45 D of single conductor

 

77-89 mm

2.6-3.0 inch

4.1.4

Binder tape

 PET binder tape 1x0.04mm

 1.6 mils

4.1.5

Overlap of binder tape

 25%

 

4.1.6

Diameter of cabling

 5.63 mm

 222 mils

5

Total cabling

5.1

number of cores

 10

10

5.2

Sequence

Phase1 + Phase 2 + control + Phase 3 + Ground

5.3

Color sequence

1 Black, 1 Red, 1 White, control, Green

5.4

lay direction

Right

 

5.5

lay length

35-40 D of single phase conductor

328-374 mm

inch

5.6

Diameter

21.2

835 mils

5.7

Binder tape

A binder tape non-woven tape 0.14mm 

5.8

Diameter over tape

22.04 mm

868 mils

6

Sheath 

6.1

material

flame resistant and sunlight resistant PVC 

6.2

Color code

Black

 

6.3

Thickness of insulation

2.08 mm

82 mils

6.4

Min thickness

1.87 mm

74 mils

6.5

Diameter over insulation

26.2 mm

1032 mils

6.6

Min diameter

26.0 mm

1023 mils

6.7

Max diameter

26.8 mm

1504 mils

7

Cable marking

AMERICAN WIRE GROUP POWER & CONTROL TRAY CABLE

7.1

Embossing

XHHW-CONDUCTORS 3 AWG (26.67mm2) 3/C & 6 AWG(13.3mm2) 1/GRND & 16 AWG (1.31mm2) 6/C TC-ER E484412(UL) 600V 90C DRY/90C WET OIL RES I SUNLIGHTRESISTANT DIRECT BURIAL JOIST PULL

7.2

Ink Jet