Construction
Conductors are concentric strand AAC (1350-H19), AAAC (either compressed or full compact depending on conductor size) or ACSR. The conductor shield shall be an extruded back semiconductor polymer meeting the physical requirements of ICEA S-61-402. Available with track-resistant high-density polyethylene (TR-HDPE) per ASTM D1248 or Track-Resistant Cross-linked Polyethylene (TK-XLPE) covering per ASTM D2656 and ICEA S-66-524. The minimum thickness of each layer at any point shall not be less than listed in the data table. The outer layer shall contain a carbon black additive, not less than 0.02% to provide the weather resistance, and track resistance.
Specification
15kV - 35kV Covered Aerial Medium Voltage Cable wire meets or exceeds all applicable ICEA specifications and the following ASTM specifications:
Item # |
Size
|
Stranding |
Conductor
|
Covering
|
Covering
|
Covering
|
Cable
|
Rated
|
Weight
|
---|---|---|---|---|---|---|---|---|---|
TW35-3-AAC-1/0-7 |
Size (AWG or kcmil) N/A 1/0 |
Stranding N/A 7 |
Conductor Diameter (mils) N/A 336 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 966 |
Rated Strength (lbs) N/A 1791 |
Weight (lb/MFT) N/A 368 |
TW35-3-AAC-2/0-7 |
Size (AWG or kcmil) N/A 2/0 |
Stranding N/A 7 |
Conductor Diameter (mils) N/A 376 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1006 |
Rated Strength (lbs) N/A 2259 |
Weight (lb/MFT) N/A 411 |
TW35-3-AAC-3/0-7 |
Size (AWG or kcmil) N/A 3/0 |
Stranding N/A 7 |
Conductor Diameter (mils) N/A 423 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1053 |
Rated Strength (lbs) N/A 2736 |
Weight (lb/MFT) N/A 464 |
TW35-3-AAC-4/0-7 |
Size (AWG or kcmil) N/A 4/0 |
Stranding N/A 7 |
Conductor Diameter (mils) N/A 475 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1105 |
Rated Strength (lbs) N/A 3447 |
Weight (lb/MFT) N/A 527 |
TW35-3-AAC-266.8-19 |
Size (AWG or kcmil) N/A 266.8 |
Stranding N/A 19 |
Conductor Diameter (mils) N/A 537 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1167 |
Rated Strength (lbs) N/A 4473 |
Weight (lb/MFT) N/A 603 |
TW35-3-AAC-336.4-19 |
Size (AWG or kcmil) N/A 336.4 |
Stranding N/A 19 |
Conductor Diameter (mils) N/A 603 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1233 |
Rated Strength (lbs) N/A 5535 |
Weight (lb/MFT) N/A 696 |
TW35-3-AAC-397.5-19 |
Size (AWG or kcmil) N/A 397.5 |
Stranding N/A 19 |
Conductor Diameter (mils) N/A 659 |
Covering Thickness Conductor Shield (mils) N/A 15 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1289 |
Rated Strength (lbs) N/A 6399 |
Weight (lb/MFT) N/A 777 |
TW35-3-AAC-477-19 |
Size (AWG or kcmil) N/A 477 |
Stranding N/A 19 |
Conductor Diameter (mils) N/A 722 |
Covering Thickness Conductor Shield (mils) N/A 20 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1362 |
Rated Strength (lbs) N/A 7524 |
Weight (lb/MFT) N/A 889 |
TW35-3-AAC-556.5-37 |
Size (AWG or kcmil) N/A 556.5 |
Stranding N/A 37 |
Conductor Diameter (mils) N/A 780 |
Covering Thickness Conductor Shield (mils) N/A 20 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1420 |
Rated Strength (lbs) N/A 8946 |
Weight (lb/MFT) N/A 987 |
TW35-3-AAC-636-37 |
Size (AWG or kcmil) N/A 636 |
Stranding N/A 37 |
Conductor Diameter (mils) N/A 835 |
Covering Thickness Conductor Shield (mils) N/A 20 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1475 |
Rated Strength (lbs) N/A 10260 |
Weight (lb/MFT) N/A 1085 |
TW35-3-AAC-795-37 |
Size (AWG or kcmil) N/A 795 |
Stranding N/A 37 |
Conductor Diameter (mils) N/A 932 |
Covering Thickness Conductor Shield (mils) N/A 20 |
Covering Thickness Inner Layer (mils) N/A 175 |
Covering Thickness Outer Layer (mils) N/A 125 |
Cable O.D. (mils) N/A 1572 |
Rated Strength (lbs) N/A 12510 |
Weight (lb/MFT) N/A 1278 |