ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
All Categories > Transmission & Distribution Cables > PowerGuard® MV Aerial Cable (Spacer Cable or Tree Wire) > 15kV PowerGuard® MV Aerial Cable 2 Layer Cable (Spacer Cable or Tree Wire) > 15kV PowerGuard® MV Aerial 2 Layer Cable (Spacer Cable or Tree Wire) - AAC > 15kV PowerGuard® MV Aerial 2 Layer Cable (Spacer Cable or Tree Wire) - AAC > View Items  

15kV PowerGuard® MV Aerial 2 Layer Cable (Spacer Cable or Tree Wire) - AAC

Check up to five results to perform an action.

Application
Used for primary and secondary overhead distribution where limited space is available or desirable for rights of way. Installed as an uninsulated conductor; however, covering is effective in preventing direct shorts and instantaneous flashovers should tree limbs or other objects contact conductors in such close proximity. The resulting close-proximity configuration minimizes the amount of space and hardware required for line installation; particularly useful in congested areas such as alleyways or tight corridors.

Construction
Conductors are concentric strand AAC (1350-H19), AAAC (either compressed or full compact depending on conductor size) or ACSR. The conductor shield shall be an extruded back semiconductor polymer meeting the physical requirements of ICEA S-61-402.  Available with track-resistant high-density polyethylene (TR-HDPE) per ASTM D1248 or Track-Resistant Cross-linked Polyethylene (TK_XLPE) covering per ASTM D2656 and ICEA S-66-524.  The minimum thickness of each layer at any point shall not be less than listed in the data table.   The outer layer shall contain a carbon black additive, not less than 0.02% to provide the weather resistance, and track resistance. 

Specification
15kV - 35kV PowerGuard® MV Aerial Cable meets or exceeds all applicable ICEA specifications and the following ASTM specifications:

  • ASTM B230 Standard Specification for Aluminum 1350–H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B232 Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR) 
  • ASTM B398 Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes
  • ASTM B399 Standard Specification for Concentric-Lay-Stranded Aluminum-Alloy 6201-T81 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded Conductors
  • ASTM D2656 Standard Specification for Cross-linked Polyethylene Insulation for Wire and Cable Rated 2001 to 35 000 V
  • ASTM D1248 Standard Specification for Polyethylene Plastics Extrusion Materials for Wire and Cable
  • ICEA S-70-547 Standard Specification for Weather Resistant Polyethylene Covered Conductors

NOTES:
Full hardware solution is available, including spacers, brackets, installation tools and hardware.  Please consult with AWG for more information.  





    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 10 of 10 1 

Item #

Size
(AWG
or
kcmil)

Stranding

Conductor
Diameter
(mils)

Covering
Thickness
Inner
Layer
(mils)

Covering
Thickness
Outer
Layer
(mils)

Cable
O.D.
(mils)

Rated
Strength
(lbs)

Weight
(lb/MFT)

TW15-2-AAC-1/0-7 1/0 7 336 75 75 636 1791 196
TW15-2-AAC-2/0-7 2/0 7 376 75 75 676 2259 230
TW15-2-AAC-3/0-7 3/0 7 423 75 75 723 2736 272
TW15-2-AAC-4/0-7 4/0 7 475 75 75 775 3447 325
TW15-2-AAC-266.8-19 266.8 19 537 75 75 837 4473 387
TW15-2-AAC-336.4-19 336.4 19 603 75 75 903 5535 466
TW15-2-AAC-397.5-19 397.5 19 659 75 75 959 6399 535
TW15-2-AAC-477-19 477 19 722 75 75 1022 7524 623
TW15-2-AAC-556.5-37 556.5 37 780 75 75 1080 8946 708
TW15-2-AAC-636-37 636 37 835 75 75 1135 10260 794
  Results 1 - 10 of 10 1 