All Categories > Medium Voltage Cables > PowerGuard® 5-35kV 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07 > PowerGuard® 5-35kV Aluminum 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07 > PowerGuard® 8kV AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07 > PowerGuard® 8kV 100% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07 > View Items  

PowerGuard® 8kV 100% AL 3-Conductor TR-XLPE Tape Shield w/Ground PVC Jacket UL MV-105/AEIC CS8-07

Check up to five results to perform an action.

Applications
Medium-Voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods.
Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart.
Installed in both exposed and concealed work, wet or dry locations, directly buried.

Construction
Conductor: Class A or B Compressed concentric stranded aluminum alloy 1350 per ASTM B 231. Stranded conductors are water-blocked with conductor filling compound.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation
Insulation: Extruded, unfilled Tree-Retardant Cross-linked Polyethylene (TRXLPE) as defined in ANSI/ICEA S-94-649
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: The metallic shield is flat uncoated 5-mil thick copper tape helically applied with minimum 20% overlap. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification - 1C w/Red, 1C w/Blue, and 1C w/None.
Grounding Conductors: Three bare stranded copper conductor, one in each interstice.
Fillers: Non hygroscopic fillers, forming a firm and cylindrical cable core.
Binder Tape: A binder tape is applied to maintain core symmetry and mechanical stability.
Jacket: Black, sunlight resistant, flame retardant PVC jacket tightly applied over the binder tape.

Standards

  • AEIC CS8, Specifications for Shielded Power Cable, 5-46kV
  • ICEA S-93-639, 5-46 kV Shielded Power Cable
  • ICEA S-97-682, Utility Shielded Power Cable Rated 5-46 kV
  • UL 1072 MV-105
  • IEEE- IEEE 383 Flame Test
  • For 105°C continuous, 140°C emergency, 250°C short-circuit operation.
  • CSA Standard C68.5-07 File # 257759 Primary Shielded and Concentric Neutral Cable for Distribution

NOTES:

Ampacities are based on three Phase Operation

In Duct (2011 NEC Table 310.15(B)(80): Three-conductor cable in plastic duct, direct-buried, 90°C conductor temperature, 20°C ambient temperature, earth RHO of 90°C-cm/Watt, and 100% load factor, and shields short-circuited.

Isolated in Air (2011 NEC Table 310.15(B)(72)): Three-conductor cable, 90°C conductor temperature, and 40°C ambient temperature, and shields grounded at one point only.

In Cable Tray: Per 2011 NEC 392.80(B)(1)(b), for single conductor cables, sizes 1/0 AWG and larger, installed in a single layer in an uncovered table tray, with a maintained space of not less than one cable diameter between individual conductors, the ampacities shall not exceed the allowable ampacities stated in 2011 NEC Table 310.15(B)(72) (Aluminum), “Isolated in Air” values noted above.






    Download PDF Download PDF   
    Email Email This Page  
    Save To Favorites Save To Favorites
  
   
  Results 1 - 12 of 12 1 

Item #

Size
AWG
or
KCMIL

Insulation
Thickness
(mil)

No. of
Ground
Wires

Size
AWG
of
Ground
Wires

Conductor
Diameter
(in)

Insulation
Diameter
(in)

Insulation
Shield
Diameter
(in)

Overall
Jacket
Diameter
(in)

Approximate
Weight (lb/MFT)

Minimum
Bending
Radius
(in)

Ampacity
90ºC
in
Duct

Ampacity
90ºC
in
Air

A4-03MV8GT10501 4 115 3 10 0.226 0.5 0.56 1.42 929 10 89 95
A2-03MV8GT10501 2 115 3 10 0.284 0.56 0.62 1.55 1095 11 115 125
A1-03MV8GT10501 1 115 3 10 0.324 0.6 0.66 1.64 1200 12 135 145
A1/0-03MV8GT10501 1/0 115 3 10 0.364 0.64 0.7 1.78 1429 13 150 170
A2/0-03MV8GT10501 2/0 115 3 8 0.408 0.69 0.74 1.88 1645 14 170 190
A3/0-03MV8GT10501 3/0 115 3 8 0.458 0.74 0.79 1.99 1834 14 195 220
A4/0-03MV8GT10501 4/0 115 3 8 0.515 0.79 0.85 2.11 2066 15 220 255
A250-03MV8GT10501 250 115 3 8 0.561 0.85 0.9 2.22 2273 16 245 280
A350-03MV8GT10501 350 115 3 7 0.664 0.95 1 2.44 2797 18 295 345
A500-03MV8GT10501 500 115 3 6 0.794 1.08 1.15 2.76 3595 20 355 425
A750-03MV8GT10501 750 115 3 5 0.974 1.27 1.34 3.22 4955 23 440 540
A1000-03MV8GT10501 1000 115 3 4 1.124 1.42 1.49 3.55 6103 25 510 635