Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation.

Standards
Secondary URD single conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
  • B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
  • Secondary UD single conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request.
Options
  • Cable in Duct (CIC)
  • Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO factor 90, 100% load factor for three conductor triplexed, 3 phase operation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Unit of Measure

Specifications

Code Name

N/A Beloit

Size
(AWG or kcmil)

N/A 4/0

Stranding

N/A 19/W

Insulation
Thickness
(mils)

N/A 80 mls

Outside
Diameter

N/A .672 Inches

Weight
(lb/1000 ft)

N/A 265 Lbs

Ampacity
Direct Burial

N/A 290 Amps

Ampacity
In Duct

N/A 225 Amps