Applications

As flame-retardant multi-conductor control, signal or power cables rated 600V, 90°C in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Also approved for use in Class I remote-control and signaling circuits per Article 725 of the NEC. Type TC cable is suitable for use in Class I and II, Division 2 hazardous locations. Cables may be installed in air, in ducts or conduits, in tray or trough, and are suitable for direct burial.

Construction

Stranded uncoated copper conductors, 30 mils FR-XLPE flame-retardant cross-linked polyethylene insulation, color coded, conductors twisted with suitable fillers where necessary to make round, cable tape, helically applied copper tape shield, PVC jacket overall, surface printed.

Specifications

  • Listed by UL as Type TC or TC-ER per Standard 1277 for Tray Cables.
  • Cables UL listed for Direct Burial.
  • Individual conductors pass UL VW-1 flame test.
  • Individual conductors UL listed as Type XHHW-2.
  • Overall jacket UL listed as Sunlight Resistant.
  • Cables with grounding conductor UL listed for Open Wiring.
  • Cables pass IEEE-383 ribbon burner flame test and ICEA 210,000 BTU/hr test.
  • Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test.
  • Cables meet requirements of ICEA S-73-532, NEMA WC57 for Control Cables.

Notes

  • Cables may be supplied with an insulated ground and marked “Open Wiring.”
  • Standard color coding is Method 1 for NEC applications per Appendix E, Table E-2 of ICEA S-73- 532(TECH I006). This color coding method omits white and green from the color sequence. A white or green conductor can be supplied on request.

Conductor
Size
AWG

N/A 10

Number
of
Conductors

N/A 2

O.A.
(mils)

N/A 45

O.D.
(inch)

N/A 0.47

Weight
(lb/1000 ft)

N/A 135