ISO 9001:2008ISO 9001
Certified
A POWERFUL SOLUTION
Applications
For use on single phase and three phase primary underground distribution systems operating at 35 kV phase to phase at 100 % insulation level. Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46 kV.
  • UL-1072 MV90
Notes
Maximum conductor temperature: 90 ºC normal continuous, 130 ºC overload, 250 ºC short circuit
Unit of Measure

Specifications

Conductor
Size AWG

N/A 2/0

Conductor
Stranding

N/A 19

Copper
Neutral
No. of
Wires

N/A 13

Copper
Neutral
Size
AWG

N/A 12

Conductor
Diameter

N/A 0.420 Inches

Diameter
Over
Insulation

N/A 1.170 Inches

Diameter
Over
Insulation
Shield

N/A 1.270 Inches

Diameter
Over
Neutral
Wires

N/A 1.400 Inches

Diameter
Over
Embedded
Jacket

N/A 1.500 Inches

Total w/o Jacket Weight

N/A 1105 Lbs

Total w/ Embedded Jacket Weight

N/A 1224 Lbs

Ampacity
1/C
Direct
Buried

N/A 250 Amps

Ampacity
1/C
Duct
Buried

N/A 195 Amps

Ampacity
1/C
Duct In Air

N/A 310 Amps

Option

N/A

  • Cable In Duct (C-I-C)
  • Parallel
  • Triplex
  • Strand Filled

FacebookTweeterLinkedInYouTube