Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductor, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Black neutrals may be specified if desired.

Standards
Secondary URD duplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 ""19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation"".
  • B-901 ""Compressed round stranded Aluminum Conductors using single input wire construction"".
  • Secondary UD duplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • ""USE-2"" per UL 854 available upon request.
Options
  • Cable in Duct
  • Abrasion Resistant
Ampacity
90ºC conductor temperature, 20ºC ambient, RHO 90, 100% load factor. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Unit of Measure

Specifications

Code Name

N/A Everett

Phase
Conductor
Size/AWG

N/A 2

Phase
Conductor
Stranding

N/A 7/w

Phase
Conductor
Insulation
Thickness

N/A 60 mls

Neutral Size AWG

N/A 2

Neutral Stranding

N/A 7/w

Neutral Insulation Thickness

N/A 60 mls

Single
Phase
Conductor

N/A .403 Inches

Outside
Diameter

N/A .806 Inches

Weight
(lb/1000 ft)

N/A 189 Lbs

Ampacity
Direct Burial

N/A 187 Amps

Ampacity
In Duct

N/A 100 Amps