Applications
Covered Line Wire is used primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.

Construction
Aluminum alloy 1350-H19 wires concentrically stranded over a steel wire core. The steel wire core is Class A Zinc coated (Code GA2). The conductor is covered with linear-low density polyethylene (LLDPE).

Standards
  • ASTM B230 – Aluminum 1350–H19 Wire for Electrical Purposes
  • ASTM B231 – Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B232 – Concentric-Lay-Stranded Aluminum Conductors, Coated-Steel Reinforced (ACSR)
  • ASTM B498 – Zinc-Coated (Galvanized) Steel Core Wire for Use in Overhead Electrical Conductors
  • CSA C60888 – Zinc-coated steel wires for stranded conductors
  • CSA C60889 – Hard-drawn aluminum wire for overhead line conductors
  • CSA C61089 – Round wire concentric lay overhead electrical stranded conductors
  • ASTM D1248 – Polyethylene Plastics Extrusion Materials for Wire and Cable

Notes

1) Dimensions and weights are subject to standard manufacturing tolerances and are subject to change without notice.
2) Resistance is calculated using metal conductivity of 61.2% IACS for EC (1350) at 20ºC and 8% IACS for steel at 20ºC.
3) Ampacities are based on 75ºC conductor temperature, 25ºC ambient, 2 ft/s wind, full sun, an emissivity of 0.91 and a coefficient of solar absorption of 0.91, at sea level. Thermal resistivity of covering is 375ºC-cm/Watt.




UPDATED 06/12/2023

Unit of Measure

Specifications

Code Name

N/A Butternut

Size
AWG /KCMIL

N/A 4

Stranding

N/A 6/1

Conductor
Diameter
(in)

N/A 0.250

Covering
Thickness
(in)

N/A 0.030

Overall
Diameter
(in)

N/A 0.310

AL
Weight
(lb/1000 ft)

N/A 38.9

STEEL
Weight
(lb/1000 ft)

N/A 18.4

NET
Weight
(lb/1000 ft)

N/A 68.8

Rated
Strength

N/A 1860

DC
Resistance
@ 20 deg C
(ohm/1000 ft)

N/A 0.4030

Ampacity
(A)

N/A 140