Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, cross-linked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.

Standards
Secondary URD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation.
  • B-901 Compressed round stranded Aluminum Conductors using single input wire construction.
  • Secondary UD quadruplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request
Options
  • Cable in Duct (CIC)
  • Abrasion Resistant
Ampacity
To determine correct ampacity by conductor size, please consult the National Electric Code, the latest edition.
Unit of Measure

Specifications

Code Name

N/A Wofford

Phase
Conductor
Size/AWG

N/A 500

Phase
Conductor
Stranding

N/A 37

Phase
Conductor
Insulation
Thickness

N/A 95 mls

Neutral Size AWG

N/A 350

Neutral Stranding

N/A 37

Neutral Insulation Thickness

N/A 95 mls

Single
Phase
Conductor

N/A .851 Inches

Outside
Diameter

N/A 2.348 Inches

Weight
(lb/1000 ft)

N/A 2174 Lbs

Ampacity
Direct Burial

N/A 467 Amps

Ampacity
In Duct

N/A 420 Amps

Option

N/A

  • Cable In Duct (CIC)
  • Abrasion Resistant